Explosion in a gas containers company

Event

Event ID
1249
Quality
Description

The event took place in centre for assembly and maintenance of empty gas cylinders. Three workers were dismantling a rack of eight hydrogen cylinders for maintenance. When woeking at the when they felt a bang and heard a gas leak. The alarm 15 minutes later, the site was evacuated after approximately an hour, the power shut off and the area was ventilated. Safety barriers were put in place to prevent traffic and firefighters intervened.
Hydrogen concentrations around 10% to 15% of the Low Flammability Level. The operator closed the cylinder's maintenance valve. 3 hours later, the hydrogen concentration was below the detector's detection limit. Firefighters left the site the emergency plan was terminated.

The operators who were present at the scene of the bang were taken to the hospital for examination. Three neighbouring businesses were evacuated for a day.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Component involved
CGH2 cylinder(s)
Failure mode
rupture & ignition
Initiating cause
inadequate or no purge
Root CAUSE analysis

The INITIATING CAUSE was the exposure of the hydrogen ballons to a flame. Someone tried to cut the string tied to a bunch of balloons with a cigarette lighter, when the flames struck one of the balloons before the whole bunch exploded. A discarded cigarette lighter was found at the scene.

Root causes
Date entry in HIAD
25/12/2025

Facility

Application
Other
Sub-application
industrial gases production
Hydrogen supply chain stage
All components affected

valve, cylinder,rack

Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Confined
Location
populated area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
3
Post-event summary

The 3 workers were hospitalised for medical controls, but were only lightly injured.

Emergency action

The alarm was called 15 minutes after the explosion, the site was evacuated after approximately an hour, the power shut off and the area was ventilated. Safety barriers were put in place to prevent traffic and firefighters intervened. Measurements of hydrogen concetrations were executed.

Lesson Learnt

Lesson Learnt

The company where the hydrogen release occurred was assembling and maintaining containers for compressed gases. Although not explicitly said by the source, it is probable that standard activities were not covering handling of various species of compressed gases and that the related working instructions were not designed for this. This would explain the lack of a check on the content of cylinders received back from customers, even though this check is easy to execute.
Moreover, an important contribution to the incident was caused by the customer company, which also did not perform any check on the successful accomplishment of the operation of emptying before shipping the cylinders. This case highlights the importance of agreement between parties, when the responsibility on safety is shared among them.

Corrective Measures

Following this incident, the operator:

(1) Modified certain maintenance valve models to make their position easier to read.
(2) Distributed a cylinder pressure monitoring procedure to all user companies.
(3) Added a measure to verify the purging of storage racks upon return by user companies or during interventions carried out by the operator at third-party sites.
(4) Implemented drills with a specialized company to prepare for similar incidents
(5) Raised staff awareness of the risk of gas being present in cylinders returned by user companies.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release pressure [MPa]
20
Probable IGNITION SOURCE
Explosion type

References

Sources categories
ARIA
Reference & weblink

Event nr 62234 of the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/62234/