Event
- Event ID
- 544
- Quality
- Description
A fire occurred in a pipe trench containing about 50 pipelines.
The pipelines were carrying a wide variety of hydrocarbons from crude oil to residuals. In addition, there were lines with steam, fuel gas, hydrogen, amine solutions and sour water pipelines.
Within 10 minutes of the fire, an explosion occurred followed by larger explosions in the pipe trench as pipelines ruptured. The fire spread to a diesel tank. The refinery had to be taken offline. The fires were extinguished after 12 hours. A lagging fire was concluded with excessive oil in the trench. The pipes ruptured due to no relief valve and being blocked in.- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- fire followed by an explosion
- Macro-region
- North America
- Country
- United States
- Date
- Component involved
- pipeline (generic)
- Failure mode
- rupture & ignition
- Initiating cause
- conventional component failure (fire)
- Root CAUSE analysis
The INITIATING CAUSE was a fire in a trench populated with several fuel pipes
The reason for the fire is not given. It could be speculated that a flammable substance leaked from one of the pipes and ignited, engulfing the other pipes. The explosions noticed after the fire started could have been caused by the individual rupture of other pipes.
The ROOT CAUSE of the fire is unknown.
- Root causes
- Unknown
- Date entry in HIAD
- 01/01/2020
Facility
- Application
- Petrochemical industry
- Sub-application
- Pipeline
- Hydrogen supply chain stage
- All components affected
hydrocarbons pipeline
- Location type
- Open
- Location
- industrial area
- Operational condition
- UNKNOWN
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Post-event summary
The refinery had to be taken offline.
The fires were extinguished after 12 hours- Emergency action
The fires were extinguished after 12 hours.
Lesson Learnt
- Corrective Measures
1. Provide adequate clearance below pipes so that drainage is adequate to prevent accumulation of oil.
2. Remove steam and other high temperature lines from main pipe alleys to reduce ignition sources.
3. Install additional fire fighting water turret monitors to improve first response fire fighting ability.
4. Provide a fire break to reduce pipe alley fire exposure.
5. Emphasize improved housekeeping, as related to free oil and oil soaked insulation.
6. Minimize piping inside tank firewalls.
In-depth data
- Release type
- gas-liquid mixture
- Involved substances (% vol)
- H2,
hydrocarbons,
steam,
fuel gas,
amine solutions - Probable IGNITION SOURCE
References
- Sources categories
- ICHEME
- Reference & weblink
Event of the UK database ICHEME.
https://www.icheme.org/knowledge/safety-centre/resources/accident-data/