Skip to main content
Clean Hydrogen Partnership

Explosion in a fertilisers plant

Event

Event ID
223
Quality
Description

The event occurred in the ammonia production unit.
A minor leak had been detected in a flange on the piping of the ammonia synthesis loop (operating at 250 bar). The company called a specialized external contractor to perform an on-stream repair of the valve. This solution was chosen because of the limited extents of the leakage and the economic costs and efforts associated to a shut-down of a very complex system.

The on-stream repair consisted in: (1) fabrication of a special bracket in two parts adapted to the dimensions of the flange of the valve, and (2) injection of filling material in the bracket around the flange (the material had to be injected at a pressure higher than the operating pressure inside the pipe). During the repair some stud bolts broke causing the escape of a jet of a gaseous mixture of unknown amount of hydrogen and nitrogen at 250 bars. The escaping mixture exploded, killing 2 workers and damaging the valves and the piping.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Component involved
flange (bolts)
Failure mode
rupture & ignition
Initiating cause
wrong installation
Root CAUSE analysis

INITIATING cause was the failure of a flange followed by the release of a nitrogen-hydrogen mixture.

The investigation revealed that two causes have probably contributed to the accident:

(1): the flange stud-bolts of the valve have been replaced by others made of a material not equivalent to the one originally specified;

(2): the maintenance company performing the repair have not taken into account the overpressure on the stud-bolts due to the injection of the filling material in the bracket.

Therefore the root cause could be identified in the lack of a proper risk assessment of the repairing operation.

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Chemical industry
Sub-application
Fertilisers production
Hydrogen supply chain stage
All components affected

flange, bolt, ammonia synthesis loop, valve, bracket

Process temperature range [C]
High temperature (100°C to 500°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

Following the detection of a small leak repairing works had been subcontracted, to be performed while the plant continued its operation.

Emergency & Consequences

Number of fatalities
2
Number of injured persons
0
Emergency action

After the explosion, the ammonia production unit was shut-down.
No off-site emergency measures were necessary.

Lesson Learnt

Corrective Measures

After the accident, the following measures were established:
- compilation of written maintenance procedures with emphasis on safety issues;
- establishment of the sequence of operations to be followed during repair of such valves.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2 75%
N2 25%
Release pressure [MPa]
25
Probable IGNITION SOURCE
Explosion type

References

Sources categories
eMARS
Reference & weblink

Event description in European database eMARS
https://emars.jrc.ec.europa.eu/en/emars/accident/view/81b0a851-01f8-620…
(accessed September 2020)

Event no. 170 in the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/176/
(accessed October 2020)