Skip to main content
Clean Hydrogen Partnership

Explosion in a cold rolling plant

Event

Event ID
951
Quality
Description

Employees were trying to open the manhole cover (600 mm diameter) of a hydrofluoric acid tank with a grinder, when an explosion occurred.
The explosion was probably caused by the presence of hydrogen formed by the acid attack of the metal. At the moment of the accident, the tank was empty, but uncleaned, and separated from the filling and ventilation pipes.

According to the eMARS report, in the course of cleaning work on the hydrofluoric acid storage tank, the residual of concentrated hydrofluoric acid remaining in the tank was diluted with water and not completely neutralized with sodium hydroxide. Subsequently, the container was sealed, after which the cleaning work was interrupted for at least two days. During this time, an explosive atmosphere formed in the tank, as a result of the reaction of the dilute hydrofluoric acid with the iron material of the container which produced hydrogen. When the cleaning work resumed, the explosive mixture was ignited presumably by the sparking due to the work with an angle grinder.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
Germany
Date
Component involved
chemical storage tank (H2SO4)
Failure mode
rupture & ignition
Initiating cause
accidental air entrance
Root CAUSE analysis

The INITIATING cause was the ignition of the accidentally formed hydrogen insider the tank.

A possible root cause of the accident would be the lack of risk assessment related to the potential formation of explosive atmosphere in the tank. Inadequate neutralisation of the residual acid and the disconnection of the tank from the venting line were contributing causes.

Root causes
Date entry in HIAD
01/01/2018

Facility

Application
Steel and metals industry
Sub-application
generic metal processing
Hydrogen supply chain stage
All components affected

hydrofluoric acid tank

Location type
Confined
Location
industrial area
Operational condition
Description of the facility/unit/process/substances

DESCRIPTION OF THE SUBSTANCE INVOLVED
Hydrofluoric acid is a solution of hydrogen fluoride in water.

Emergency & Consequences

Number of fatalities
2
Number of injured persons
2
Currency
Euro
Property loss (onsite)
2.000
Post-event summary

Two employees, thrown by the blast of the explosion were killed and two others injured. The tank cover perforated the roof of the neighbouring production hall located 60 m away.

Emergency action

The on-site firefighters evacuated the employees and secured the site.

Lesson Learnt

Lesson Learnt

When a metal enters in contact with hydrofluoric acid, one of the reaction products is hydrogen.
Fe + 2HF -> FeF2 + H2
If the reaction occurs in and enclosed space, such as the tank of this incident, hydrogen gas can accumulate in the equipment and reach the lower explosive limit when the equipment is open to air. The amount of energy required to ignite the gas mixture is small and the result is an explosion that will damage equipment.

Therefore, an adequate risk assessment needs to be performed when dealing with the acid, aiming at assessing the adequacy of measures such as purging of the tank before maintenance, availability of enough ventilation, detection of flammable gases, and safety training.

Corrective Measures

The corrective action adopted by the plant was to provide suction to prevent the formation of an explosive atmosphere inside the containers. Maintenance would then take place with the exhaust air switched on.

In-depth data

Release type
gas
Involved substances (% vol)
H2 (assumed)
Probable IGNITION SOURCE
Explosion type
Deflagration

References

Sources categories
eMARS
Reference & weblink

Event description in the European database eMARS
https://emars.jrc.ec.europa.eu/en/eMARS/accident/view/19179a7d-a997-157…
(accessed October 2020)

Event from German database ZEMA
https://www.infosis.uba.de/index.php/de/site/2854/zema/index/26448.html
(accessed December 2024)

RP ONLINE News, 5 Mai 2010 (in German),
https://rp-online.de/nrw/staedte/krefeld/thyssen-kessel-deckel-erschlae…
(accessed October 2020)