Skip to main content
Clean Hydrogen Partnership

Event

Event ID
644
Quality
Description

A vapour explosion, followed by a fire, occurred at a drier in a plant making titanium sponge. When titanium containing water was put into the drier, it came to contact with the edge of the protecting tube of the inside thermometer, generating sparks which ignited the titanium sponge. The red-hot titanium sponge melted the drier to leak out, and reacted with water spilled from the fractured drier, producing hydrogen gas. This led to the vapour explosion scattering titanium, which ignited the nearby products of titanium.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Asia
Country
Japan
Date
Component involved
chemical storage tank
Failure mode
leak & ignition
Initiating cause
run-away reaction
Root CAUSE analysis

The ROOT CAUSE was a fault of the whole design. Moreover, management of the operations should have realised the intrinsic hazard of the operations, and intervene.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Steel and metals industry
Sub-application
titanium production
Hydrogen supply chain stage
All components affected

titanium sponge, dryer,

Location type
Unknown
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
1
Number of injured persons
4

In-depth data

Release type
gas-solid mixture
Involved substances (% vol)
H2,
H2O,
titanium
Probable IGNITION SOURCE
Explosion type

References

Sources categories
RISCAD
Reference & weblink

Orignal source lost. RISCAD is closed.