Event
- Event ID
- 340
- Quality
- Description
A stainless steel manifold ruptured during experimental operation. The manifold was made of stainless steel and had a diameter of three inch (7.5 cm). The hardware was off-the-shelf, slightly modified, pre-safety checked and analysed by the supply vendor. The test apparatus was in an altitude tank at simulated altitude conditions at the time of the mishap.
At the moment of the explosion, it contained a mixture of hydrogen (0.27 lbs, 0.12 kg) and air (0.26 lbs) at 350 psia (24 bar). Damage was restricted to the manifold and some of the experimental package valves.
- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- North America
- Country
- United States
- Date
- Component involved
- manifold
- Failure mode
- internal explosion
- Initiating cause
- inadequate or wrong design
- Root CAUSE analysis
The INITIATING CAUSE of the rupture was a detonation of an accidentally formed hydrogen and air mixture inside the manifold.
The investigation team determined that the principal cause of the mishap was the lack of backflow prevention devices in the hydrogen and air supplies to the test package. That deficiency permitted the accumulation of the detonation charge within the manifold. A contributing factor was the deviation from preplanned test procedure by the test crew while attempting to make the device work.
- Root causes
- Date entry in HIAD
- 01/11/2025
Facility
- Application
- Non-road vehicles
- Sub-application
- Aerospace
- Hydrogen supply chain stage
- All components affected
manifold, valves
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Location type
- Confined
- Location
- industrial area
- Operational condition
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Post-event summary
Damage was restricted to the manifold and some of the experimental package valves.
- Emergency action
none
Lesson Learnt
- Lesson Learnt
The source report the following lesson:
Even a "Small amounts of hydrogen and air (much less than a kg) and an ignition source can cause detonation and damage in a confined area."- Corrective Measures
The source recommended following:
"Design backflow prevention devices in propellant piping systems to prevent the accumulation of combustible mixtures in confined areas."
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Released amount (kg)
- 0.12
- Release temperature [°C]
- 25
- Probable IGNITION SOURCE
- Explosion type
References
- Sources categories
- Investigation report
- Reference & weblink
NASA lesson report 168 at
https://llis.nasa.gov/lesson/168
(accessed November 2025)