Conventional fire on a CGH2 trailer

Event

Event ID
1146
Quality
Description

The trailer experienced a tire/wheel fire at the rear of the tube trailer. The fire deteriorated the hand valve packing on one of the tube causing a slow leak of hydrogen. The trailer consisted of 10 tubes and only 1 of the tubes leaked. The road was closed due to the fire. [Note of the event validator: the PHMSA report does not mention any hydrogen ignition. However, the local news quote a fire brigade report which speaks of two fires: the one caused by the orignal conventional axle fire, easy to be extinguised, and a second one engulphing the trailer cabinet, which took much more time to get under control]

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
North America
Country
United States
Date
Component involved
valve (generic)
Failure mode
rupture & ignition
Initiating cause
conventional component failure (fire-tyres)
Root CAUSE analysis

The INITIATING CAUSE was a conventional fire on tire following brake failure. One gasket in the packing assembly was damaged by the heat, what resulted in a very small hydrogen leak. The ROOT CAUSE is unknown.

Root causes
Unknown
Date entry in HIAD
25/10/2024

Facility

Application
Hydrogen transport and distribution
Sub-application
CGH2 tube trailer
Hydrogen supply chain stage
All components affected

valve

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Open
Location
highway or similar
Operational condition
Description of the facility/unit/process/substances

DESCRIPTION OF THE UNIT This trailer unit consisted of 10 tubes. The individual report provides values in Gas-Pound, which are easy to convert into kg of hydrogen. According to this report, the total nominal transport capacity was 640 pounds (290 kg), but the quantity transported at the moment of the incident was 420 pounds (191 kg).

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
US$
Property loss (onsite)
173.500
Emergency action

The road was closed due to the tire fire. No active action was taken regarding the very small hydrogen leak. And the hydrogen was left disperse into the atmosphere

Lesson Learnt

Lesson Learnt

This small incident, almost a near miss considering the very low amount of hydrogen vented, did not have any noticeable consequence. Nevertheless, similar cases started with conventional fires caused the mass venting of the whole hydrogen load, because the pressure relief valve were thermally or pressure-activated. Such a case has to be avoided when the trailers are in a confined space, such as a tunnel.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Released amount (kg)
10.9
Release temperature [°C]
25
Probable IGNITION SOURCE

References

Sources categories
PHMSA
Reference & weblink

Incident E-2019080616 of the US Pipeline and Hazardous Materials Safety Administration PHMSA: https://portal.phmsa.dot.gov/analytics/saw.dll?Portalpages&PortalPath=%2Fshared%2FPublic%20Website%20Pages%2F_portal%2FHazmat%20Incident%20Report%20Search (accessed September 2024)

Demopolis Times new https://www.demopolistimes.com/2019/08/08/dfd-responds-to-truck-business-fires/ (accessed July 2025)