Skip to main content
Clean Hydrogen Partnership

Accidental production of hydrogen from batteries

Event

Event ID
813
Quality
Description

A release of hydrogen and steam occurred in the battery room of a nuclear power plant around 21 h. Site agents neutralised the batteries. Noting the failure of the smoke extractor, public firefighters ventilated the room.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
Europe
Country
France
Date
Component involved
battery
Failure mode
rupture, no ignition
Initiating cause
over-heating
Root CAUSE analysis

The INITIATING CAUSE was the overheating of batteries, which produced the release of water of the electrolyte and hydrogen.
The ROOT CAUSE is not provided. The fact that a fume detector, which had the obvious function to detect this type of events, was not function suggests inadequacy of inspection and maintenance.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Power plant
Sub-application
Nuclear power plant
Hydrogen supply chain stage
All components affected

battery room, smoke extractor

Location type
Confined
Location
industrial area
Operational condition
UNKNOWN
Description of the facility/unit/process/substances

DESCRIPTION OF THE SYSTEM
The report does not mention the type of batteries used and their functions. It can only be said that it was an energy storage system, possible as alternative or additonal power supply in case of emergency. The mentioned accidental production of steam and hydrogen could be possibly suggest a lead-acid battery system.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

The property loss was related to the need to replace (partially) the battery storage system.

Emergency action

Site agents neutralised the batteries. Public firefighters ventilated the room with their own means. Normal operation was restored at 22:50.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2,
steam
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

ARIA data base event no. 42040
https://www.aria.developpement-durable.gouv.fr/accident/42040_en/?lang=…
(accessed October 2025)