Event
- Event ID
- 966
- Quality
- Description
Heavy rains (more than 600 mm in 1 day) had flood a factory manufacturing calcium core electrical conductors. The power supply was cut off. The water came into contact with the calcium stored in 150 kg containers, producing hydrogen (7.5 kg per container). The heat of reaction ignited the gas. The fire was extinguished with sand.
- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- fire
- Macro-region
- Asia
- Country
- South Korea
- Date
- Component involved
- chemical storage tank
- Failure mode
- rupture & ignition
- Initiating cause
- accidental hydrogen formation
- Root CAUSE analysis
The ARIA report (see references) identifies as possible root cause the fact that the calcium containers were the probably insufficiently sealed to deal with the abnormal quantity of water cumulated.
- Root causes
- Date entry in HIAD
- 01/01/2018
Facility
- Application
- Electrical, electronics and micro-electronics industry
- Sub-application
- electrical components production
- Hydrogen supply chain stage
- All components affected
calcium storage containers
- Location type
- Unknown
- Location
- populated area
- Operational condition
- Pre-event occurrences
Heavy rains (more than 600 mm in 1 day) had flood the factory.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Probable IGNITION SOURCE
References
- Sources categories
- ARIA
- Reference & weblink
Event description in the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/14162/