Event
- Event ID
- 1234
- Quality
- Description
This near miss affected a testing installation for liquid hydrogen. A leak developed on a valve installed on a purge line connected with a LH2 storage tank. This shut-off valve served to discharge hydrogen into the exhaust stack of the installation, in case LH2 evaporation from the filling or withdrawal hose was causing excessive pressure. It was also serving a purging purpose, by flushing the filling hose with gaseous hydrogen before filling the cylinder with LH2.
The valve was more than 20 years and was not sealing properly under cryogenic conditions, causing hydrogen gas to escape from the threated connection between the valve stem and the valve case. The valve failed on two internal parts: the metal diaphragm and the O-ring that served as a seal (a sealing with thoric geometry). The metal diaphragm no longer seated properly against the valve seat causing leakage.- Event Initiating system
- Classification of the physical effects
- Unignited Hydrogen Release
- Nature of the consequences
- Macro-region
- Europe
- Country
- Germany
- Date
- Component involved
- cryogenic valve
- Failure mode
- leak, no ignition
- Initiating cause
- material degradation (ageing)
- Root causes
- Unknown
- Date entry in HIAD
- 14/12/2025
Facility
- Application
- Laboratory / R&D
- Sub-application
- LH2 storage
- Hydrogen supply chain stage
- All components affected
tank, piping
- Process temperature range [C]
- cryogenic temperature (below -50°C)
- Process pressure range [MPa]
- low to medium pressure (below 2 MPa)
- Location type
- Open
- Location
- industrial area
- Operational condition
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Post-event summary
A new valve and a new piping system ahd to be installed.
- Emergency action
none required
Lesson Learnt
- Corrective Measures
A new model from the same company had to be purchased, because the model of the defective valve was discontinued. The new valve was larger in outer dimensions than the old one. Therefore, the pipe routing around the valve had to be modified. A total of three new welds and an approximately 25 cm long, multiply bent new pipe section were required for installation. The tightness of the welds, the pipe, and the valve against the environment was successfully tested using a calibrated leak detector with a measuring range of from 0 to 1000 ppm H2.
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Probable IGNITION SOURCE
References
- Sources categories
- Investigation report
- Reference & weblink
Infrmation provided by project leader by email (6 October 2025) - CONFIDENTIAL