LH2 leak from a stationary tank

Event

Event ID
1231
Quality
Description

A leak occurred near the bottom of a stationary liquid hydrogen tank with a capacity of a 6,000-gallon. The leak was localised on a valve and was visible due to the air condensation forming white clouds rosing upward and dissipating. Ignition did not occur.

Fire fighters tested hydrogen concentration in air around the leaking place and determined it to be safe. After which, plant workers shut off a secondary valve, isolating the leaking valve.
Preliminary investigations indicated that a faulty O-ring may have been the cause.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
North America
Country
United States
Date
Component involved
cryogenic valve
Failure mode
rupture, no ignition
Initiating cause
material degradation (generic)
Root CAUSE analysis

Nothing is known on the ROOT CAUSE. The fact that the leak was identified first at the bottom of the tank, and later also from the top of the tank (see reference), suggest a possible degradation of the thermal isolation capacity of the external shell of the tank. But it cannot be confirmed by unavailability of the investigation report.

Root causes
Unknown
Date entry in HIAD
31/10/2025

Facility

Application
Hydrogen stationary storage
Sub-application
LH2 storage
Hydrogen supply chain stage
All components affected

tank

Process temperature range [C]
cryogenic temperature (below -50°C)
Process pressure range [MPa]
low to medium pressure (below 2 MPa)
Location type
Open
Location
populated area
Operational condition
Pre-event occurrences

the quantity of hydrogen in the tank during leak is unknown.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Emergency action

The original emergency strategy of the company was to let the tank bleed. Eventually, the company called the local fire department. The onsite building, a neighbouring business and a residence were evacuated, and police blocked nearby streets. Major concern was the possibility to produce ignition source able to ignite the leaking hydrogen.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release pressure [MPa]
<1.0
Probable IGNITION SOURCE

References

Sources categories
News
Reference & weblink

ISSS source news of 23 Dec 2013
https://www.isssource.com/leaking-valve-leaks-hydrogen/