Fire from the storage area of a HRS

Event

Event ID
1163
Quality
Description

A fire occurred at a hydrogen refuelling station for buses. The incident was initially reported as an explosion due to a loud noise and vibrations felt in nearby buildings. However, subsequent investigations clarified that the fire resulted from a hydrogen venting through a safety valve of the station hydrogen storage. The fire was extinguished within approximately 50 minutes, and no casualties were reported. Some damage occurred to the roof of the storage building.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Asia
Country
South Korea
Date
Component involved
PRD (valve)
Failure mode
rupture & ignition
Initiating cause
unknown
Root CAUSE analysis

The INITIATING CAUSE of the fire was a hydrogen venting through the safety valve.
The ROOT CAUSE is unknown.

Root causes
Unknown
Date entry in HIAD
01/02/2025

Facility

Application
Hydrogen refuelling station
Sub-application
CHG2 storage
Hydrogen supply chain stage
All components affected

safety valve

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium pressure (2 to 10 MPa)
Location type
Semiconfined
Location
populated area
Operational condition
Description of the facility/unit/process/substances

DESCRIPTION OF THE FACILITY
HRS compression and storage capacity of 180 kg/h with two refueling lines providing 90 kg/h each. designed for commercial vehicles like trucks and buses (https://fuelcellsworks.com/2024/10/14/fuel-cells/korea-busan-new-port-completes-first-hydrogen-refueling-station-for-cargo-trucks).
From the pictures of the YTN video, the station storage system seems to consist in hydrogen tube trailers, wit the typical vent system for each of the tube releasing hydrogen inside the building. Another type of longer tubes is visible aswell.
The building appears to be only partially covered by a roof. storage pressure is unknown (possiblyaround 40 MPa), the hydrogen inventory, the safety systems in place.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

Some damage to the roof structure is visible.

Emergency action

The fire brigade intervened extinguishing the fire within approximately 50 minutes,

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE