Event
- Event ID
- 1090
- Quality
- Description
The event occurred at the hydrogenation unit of a pharmaceutical company.
145 kg of hydrogen were released at the atmosphere at the gas circulation pump, due to a maintenance error. A specialist company (third-party company), had replaced the cylinder head of pump, but during assembly they did not re-installed the prescribed temperature sleeve for the thermometer (the temperature sleeve is the pressure-bearing element).
The safety flare of the affected plant was triggered, the plant operations management and plant fire brigade were called on duty, the hydrogen supply to the neighbouring hydrogenation unit was stopped and the system was switched to circular operation.- Event Initiating system
- Classification of the physical effects
- Unignited Hydrogen Release
- Nature of the consequences
- leak no ignition
- Macro-region
- Europe
- Country
- Germany
- Date
- Component involved
- compressor / booster / pump
- Failure mode
- rupture, no ignition
- Initiating cause
- wrong installation
- Root CAUSE analysis
The INITIATING CAUSE was an error during re-assembling of the system after maintenance.
A possible contributing CAUSE could be a lack of maintenance instructions, or their shortcoming.- Root causes
- Date entry in HIAD
- 01/07/2024
Facility
- Application
- Chemical industry
- Sub-application
- Farmaceutical manufacturing
- Hydrogen supply chain stage
- All components affected
hydrogen recirculation pump
- Location type
- Unknown
- Location
- populated area
- Operational condition
- Pre-event occurrences
Maintenance works had been completed by a third party.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Property loss (onsite)
- 0
- Post-event summary
Only operative costs due to loss of hydrogen and production stop.
- Emergency action
The safety flare was triggered, so that the leaked hydrogen could be released safely.
Factory fire brigade and factory operations management were called on site.
The hydrogen supply was stopped at the neighbouring hydrogenation plants and the system was operated in closed-loop mode.
Lesson Learnt
- Corrective Measures
To develop an assembly checklist together with the external (third party) company.
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Released amount (kg)
- 145
- Probable IGNITION SOURCE
References
- Sources categories
- ZEMA
- Reference & weblink
Event from German database ZEMA
https://www.infosis.uba.de/index.php/en/binaries/asset/zema_ereignis/16…
(accessed December 2023)