Description

A lightning strike caused a voltage drop on the power supply of a chlorine-alkali plant using the mercury process. The emergency electrical system was activated, though restoring the external supply voltage in less than 200 ms rendered the entire system inconsistent; some units were operating normally, but all units connected to the emergency devices (including the mercury pump) remained idle.
An explosive mix of 500 kg of chlorine and an unknown amount of hydrogen accumulated inside the low-pressure chlorine treatment circuit. When the mix exploded, it injured two employees and destroyed the whole circuit (damage: 237 000 euros).

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
Germany
Date
Component involved
electrolytic cell
Failure mode
rupture & ignition
Initiating cause
extreme environmental conditions (lightning)
Root CAUSE analysis

The INITIATING cause was the loss of power due to lightning. The power recovery system was not considering that several components would have not properly reacted to micro-losses.

Root causes
Date entry in HIAD
01/07/2024

Facility

Application
Chemical industry
Sub-application
Chlorine production
Hydrogen supply chain stage
All components affected

mercury pump

Process temperature range [C]
Above ambient temperature (50°C to 100°C)
Location type
Confined
Location
industrial area
Operational condition
Pre-event occurrences

because of a lightning, a power loss had occurred, followed by the activation of the emergency electrical system.

Emergency & Consequences

Number of fatalities
2
Number of injured persons
0
Currency
Euro
Property loss (onsite)
237.000
Post-event summary

Two employees injured and the whole electrolyser circuit destroyed.

Emergency action

Not reported, probably none.

Lesson Learnt

Lesson Learnt

:
According to ARIA, tis accident demonstrated the need to improve the simple binary approach (i.e. on/off) in term of power availability. It is necessary to incorporate short-duration voltage drops (electrical disturbances) into the safety reports.
An installation's emergency power supply must be designed by integrating a SIL 2 safety integrity level (according to the Standards IEC 61508 / 61511).

Corrective Measures

The site operator extended personnel training modules to include the facility's operating details, in a step to better cope with unidentified defects.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2,
Cl2
Release temperature [°C]
25
Probable IGNITION SOURCE
Explosion type

References

Sources categories
ARIA
Reference & weblink

Event 40197 of the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/40197/
(accessed July 2023)

Event from German database ZEMA
https://www.infosis.uba.de/index.php/de/site/2854/zema/index/16137.html
(accessed December 2024)