Event
- Event ID
- 1075
- Quality
- Description
A lightning strike caused a voltage drop on the power supply of a chlorine-alkali plant using the mercury process. The emergency electrical system was activated, though restoring the external supply voltage in less than 200 ms rendered the entire system inconsistent; some units were operating normally, but all units connected to the emergency devices (including the mercury pump) remained idle.
An explosive mix of 500 kg of chlorine and an unknown amount of hydrogen accumulated inside the low-pressure chlorine treatment circuit. When the mix exploded, it injured two employees and destroyed the whole circuit (damage: 237 000 euros).- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- Europe
- Country
- Germany
- Date
- Component involved
- electrolytic cell
- Failure mode
- rupture & ignition
- Initiating cause
- extreme environmental conditions (lightning)
- Root CAUSE analysis
The INITIATING cause was the loss of power due to lightning. The power recovery system was not considering that several components would have not properly reacted to micro-losses.
- Root causes
- Date entry in HIAD
- 01/07/2024
Facility
- Application
- Chemical industry
- Sub-application
- Chlorine production
- Hydrogen supply chain stage
- All components affected
mercury pump
- Process temperature range [C]
- Above ambient temperature (50°C to 100°C)
- Location type
- Confined
- Location
- industrial area
- Operational condition
- Pre-event occurrences
because of a lightning, a power loss had occurred, followed by the activation of the emergency electrical system.
Emergency & Consequences
- Number of fatalities
- 2
- Number of injured persons
- 0
- Currency
- Euro
- Property loss (onsite)
- 237.000
- Post-event summary
Two employees injured and the whole electrolyser circuit destroyed.
- Emergency action
Not reported, probably none.
Lesson Learnt
- Lesson Learnt
:
According to ARIA, tis accident demonstrated the need to improve the simple binary approach (i.e. on/off) in term of power availability. It is necessary to incorporate short-duration voltage drops (electrical disturbances) into the safety reports.
An installation's emergency power supply must be designed by integrating a SIL 2 safety integrity level (according to the Standards IEC 61508 / 61511).- Corrective Measures
The site operator extended personnel training modules to include the facility's operating details, in a step to better cope with unidentified defects.
In-depth data
- Release type
- gas mixture
- Involved substances (% vol)
- H2,
Cl2 - Release temperature [°C]
- 25
- Probable IGNITION SOURCE
- Explosion type
References
- Sources categories
- ARIA
- Reference & weblink
Event 40197 of the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/40197/
(accessed July 2023)ARIA full report
https://www.aria.developpement-durable.gouv.fr/accident/40197/
(accessed July 2023)Event from German database ZEMA
https://www.infosis.uba.de/index.php/de/site/2854/zema/index/16137.html
(accessed December 2024)