Fire in the electrical transformer of a metallurgical plant

Event

Event ID
1068
Quality
Description

A fire broke out on a transformer transforming 225 kV into 15 kV in a metallurgical plant. This transformer supplies electrical power the site and to a neighbouring factory.
In the following three hours, staff brought the fire under control with CO2 extinguishers, the internal emergency plan was activated, and the firefighters ventilated the premises and took readings of the flames using a thermal camera.
Meanwhile, however, the shutdown of the electrical installation caused the stop of the operation of an electrolysis unit using zinc sulphate. This unplanned stop of the process caused the generation of hydrogen at slow rate: a change from 0 to 8% LEL in 3 hours was detected.
For more than an hour, the staff, assisted by a specialised company, was busy in empting 82 tanks of 25 m³ each with the company's pump truck. After that, the electrical installation was put back into service and all the plant processes were checked.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
Europe
Country
France
Date
Component involved
electrolytic cell
Failure mode
rupture, no ignition
Initiating cause
conventional component failure (electricity, power)
Root CAUSE analysis

The presence of a cat in the transformer caused the fire to start.
The formation of hydrogen was due to the unplanned stop of the electrolyser.
The root cause can only be guessed, in between design or management shortcoming for not having foresees the risk of the possibility of sudden stop to zinc production facility.

Root causes
Unknown
Date entry in HIAD
01/07/2024

Facility

Application
Steel and metals industry
Sub-application
generic metal processing
Hydrogen supply chain stage
All components affected

transformator, zinc electrolysis

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

A lack of power supply from the transformer on fire was at the basis of the incident.

Description of the facility/unit/process/substances

DESCRIPTION OF THE PROCESS
The process involved in this incident was an industrial process called electrowinning, used for extracting metals from their ore by means of electrolysis.
In the electrolysis of zinc sulphate (ZnSO4), Zn+ ions in the electrolyte are reduced to metallic Zn at the cathode, while oxygen forms at the anode, with H2SO4 (and hydrogen) as by-product.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
1
Post-event summary

An internal firefighter, slightly inconvenienced by the fumes during his intervention, was taken to hospital as a precaution.
No technical unemployment, only production losses in the two metallurgical plants.

Emergency action

10:00 - Fire on the transformer transforming
Fire under control by means of CO2 extinguishers. The internal emergency plan was activated. The firefighters ventilated the premises and took readings of the flames using a thermal camera.
From 12.45 to 14:00, the staff, assisted by a specialized company, worked to eliminate the causes of the hydrogen production from the zinc electrolysers by empting the supply tanks.
14:15 - Electrical installation put back into service and all the plant processes checked.
14:30 - Firefighters left the site.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

Event 59092 of the French database ARIA
thttps://www.aria.developpement-durable.gouv.fr/accident/59092/
(accessed July 2023)