Cooling power loss in a foundry

Event

Event ID
1061
Quality
Description

This near miss occurred at metal smelting unit of a foundry.
At 9:45 a.m., due to a power outage, the cooling pumps of two furnaces containing nickel and chromium stopped. One of the two furnaces was at the end of the smelting cycle. The temperature of the metal was 1300°C.
Due to the stop of the cooling system, water from the public network took over the cooling function, but was not efficient, causing the cooling coil to overheat.
At this point, the risk was a contact between the molten metal and the water contained in the coil, which could have generated hydrogen, its ignition followed by an explosion.
Therefore, the operator triggered the evacuation alarm and alerted the firefighters.
The emergency services provide external cooling with water and perform natural ventilation followed by mechanical ventilation. After approximately two hours, the furnace cooled, the metal froze and the risk of explosion avoided. After additional two hours, the firefighters' intervention was over.

Event Initiating system
Classification of the physical effects
No Hydrogen Release
Nature of the consequences
Macro-region
Europe
Country
France
Date
Component involved
reactor / oven / furnace / test chamber
Failure mode
damage, no release
Initiating cause
over-heating
Root CAUSE analysis

The initiating cause of the event was a malfunction in an electrical cabinet, which caused the shutdown of the 380 V power supply to the plant. Due to the lack of power, the cooling pumps of the melting furnace stopped.
The replacing flow of city water was insufficient to stabilise furnaces temperature because a valve was not fully open. Nobody verified the operation of this valve, because the attention of the personnel was focussed on the electrical failure.

Root causes
Date entry in HIAD
01/07/2024

Facility

Application
Steel and metals industry
Sub-application
Steel metallurgy
Hydrogen supply chain stage
All components affected

metals furnace, colling coils

Process temperature range [C]
Ultra-high temperature (above 1000°C)
Process pressure range [MPa]
low to medium pressure (below 2 MPa)
Location type
Confined
Location
industrial area
Operational condition
Pre-event occurrences

The near miss occurred following a power cut.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Property loss (onsite)
0
Emergency action

Therefore, the operator triggered the evacuation alarm and alerted the firefighters. A 150 m security perimeter was set up, resulting in the confinement and evacuation of 6 homes and 115 people (employees and residents). Two bus lines were diverted and the traffic on the nearby road interrupted.
The emergency services provide external cooling with water and perform natural ventilation followed by mechanical ventilation.
Around 11:30 a.m., the furnace cooled, the metal froze and the risk of explosion avoided.
Around 12:30 p.m., staff was authorised to return to the premises to take their personal belongings and leave the site.
Around 1:30 p.m., the firefighters' intervention was over.
An interruption of work of 4 days was decided for 90 people.

Lesson Learnt

Corrective Measures

After the event, the operator adopted the following corrective measures:
• changed the water inlet valve so that its opening could be easily checked;
• revised its check lists in case of an incident;
• implemented training to improve responsiveness and targeted more frequently exercises;
• prioritised cooling above any other action in the event of an incident.

In-depth data

Release type
no release
Release temperature [°C]
1300
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

Event 60199 of the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/60199/
(Accessed Feb 2026)