Event
- Event ID
- 1060
- Quality
- Description
An in-line inspection of the hydrogen pipeline was being conducted and prior to the last run of the in-line inspection tool (magnetic flux leakage), hydrogen gas was released and ignited from a blind flange connection failure on a temporary separator filter installed at the receiver site. The fire was immediately identified by on-site personnel. There were no injuries. The pipeline section was isolated and de-pressurised to the facility flare. Local emergency responders were dispatched and contained and extinguished the fire. The fire affected the station piping and equipment in the surrounding area. Repairs and/or replacement of affected piping and equipment were completed and re-commissioned.
- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- fire
- Macro-region
- North America
- Country
- United States
- Date
- Component involved
- pipeline (flange)
- Failure mode
- rupture
- Initiating cause
- unknown
- Root CAUSE analysis
Failure of a blind flange connection, which had been temporarily installed to allow for an in-line inspection. According to the PHMSA report, there was no reason for an investigation, because there was no indication that the actions of the controller(s) or control room were the cause of, or a contributing factor to, the incident. The most logic explanation of the failure would then be a wrong installation of the temporary flange.
- Root causes
- Date entry in HIAD
- 01/07/2024
Facility
- Application
- Hydrogen transport and distribution
- Sub-application
- H2 delivery to customers
- Hydrogen supply chain stage
- All components affected
H2 pipeline
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Process pressure range [MPa]
- medium to high pressure (10 to 50 MPa)
- Location type
- Open
- Location
- countryside or desert
- Operational condition
- Pre-event occurrences
The incident occurred during an inline inspection.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Currency
- US$
- Property loss (onsite)
- 1.451.027
- Emergency action
The pipeline section was isolated and de-pressurised to the facility flare. Local emergency responders were dispatched and contained and extinguished the fire. The fire affected the station piping and equipment in the surrounding area.
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Released amount (kg)
- 1974
- Release temperature [°C]
- 25
- Release pressure [MPa]
- 10.2
- Probable IGNITION SOURCE
References
- Sources categories
- PHMSA
- Reference & weblink
US Pipeline and Hazardous Materials Safety Administration PHMSA: https://www.phmsa.dot.gov/safety-reports/pipeline-failure-investigation-reports