This entry refer to a series of events occurred before the date given, which corresponds to the publication of the evidences at the Int. Conference on Hydrogen Safety 2015.
The nozzle/receptacle connection froze when refuelling the on-board hydrogen storage system at the lowest precooling temperature of -40 C.
However, freezing did not cause apparatus damage nor hydrogen leakage. The nozzle/receptacle is thus able to fuel safely even if the nozzle/receptacle is stuck due to ice.- Event Initiating system
- Classification of the physical effects
- No Hydrogen Release
- Nature of the consequences
- Macro-region
- Asia
- Country
- Japan
- Date
- Component involved
- dispenser (nozzle)
- Failure mode
- n.a.
- Initiating cause
- ice formation
- Root CAUSE analysis
The low temperature of the hydrogen caused the water vapour in the atmosphere to freeze around the nozzle-receptacle connection. Under specific environmental conditions creating high humidity, the quantity of ice forming does not allow for decoupling of the connection after the refuelling.
- Root causes
- Date entry in HIAD
- 01/06/2023
Facility
- Application
- Hydrogen refuelling station
- Sub-application
- Hydrogen dispenser
- Hydrogen supply chain stage
- All components affected
nozzle - receptacle connection
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Location type
- Open
- Location
- populated area
- Operational condition
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Post-event summary
Despite the impossibility to decouple the connection, no damage is caused to the components. It is enough to wait for de-icing.
- Emergency action
It would be enough to wait for the melting of the ice.
Lesson Learnt
- Lesson Learnt
Under certain environmental conditions, air humidity can precipitate as ice around the nozzles/receptacle connection.
The results of the research presented at the ICHS2015 confirmed that the possibility of hydrogen leakage or damage to the apparatus during nozzles/receptacle connection freezing is low and that it is safe. Freezing at the hydrogen station will only prolong fuelling time.- Corrective Measures
The standards prescribing nozzle - receptacle designs were adapted.
In-depth data
- Release type
- no release
- Release temperature [°C]
- 25
- Probable IGNITION SOURCE
References
- Sources categories
- Scientific article
- Reference & weblink
paper 346 presented at the Int. Conference onHydrogenSafety ICHS2015