Release and fire at a flexible hose during hydrogen transfer

Event

Event ID
1003
Quality
Description

A hydrogen leak occurred at a tube bundle container at the loading and unloading bay of a PSA (Pressure Swing Adsorption) hydrogen production plant.
During the hydrogen filling process, a worker in charge noticed the leak in the filling hose of one of the trailers after an abnormal noise. After 22s, the hose connected to that trailer broke, and moved rapidly towards another trailer. less than 5 minutes later, the broken hose was flung in front of the other trailer and the leaking hydrogen gas started to burn. After only 5s, the hydrogen leaking from the loading and unloading ports on first trailer caught fire and burned.
The metal hose fractured, the hose was flung around, and hit an object, which caused the spark which ignited the hydrogen.
This is a case of delayed ignition: from the moment in which the hydrogen leak was detected to the first ignition took 5 minutes.
The fire resulted in damage to the pipes, valves and other accessories of the two hydrogen bundle containers.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Asia
Country
China
Date
Component involved
hose (trailer)
Failure mode
rupture & ignition
Initiating cause
inadequate or wrong design
Root CAUSE analysis

the INITIATING CAUSE of the fire was the rupture of a flexible filling hose. The hose could not meet the working pressure of 22 MPa. When the pressure reached 17.5 MPa, the hose broke off, causing a release of hydrogen. The company bought and used metal hoses produced by a machinery fittings manufacturing company. They were cheap and burst when they were filled to 7.5MPa pressure. This reveals that the enterprise's quality and safety awareness was not strong, the risk assessment was not thoroughly performed, the control and the mitigation measure was not in place or not well-designed.

Root causes
Date entry in HIAD
24/08/2024

Facility

Application
Hydrogen transport and distribution
Sub-application
CGH2 tube trailer
Hydrogen supply chain stage
All components affected

flexible, trailer

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium pressure (2 to 10 MPa)
Location type
Open
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
yuan
Property loss (onsite)
217.000.000
Post-event summary

Approximately 26 Meuro

Emergency action

The emergency measures were taken effectively. The fire was completely extinguished approximately 1 hour after its start.

Lesson Learnt

Lesson Learnt

The investigation found the company was using cheap flexible which were not designed for the pressure used during hydrogen transfer. This reveals that the enterprise's quality and safety awareness was not strong, the risk assessment was not thoroughly performed, the control and the mitigation measure was not in place or not well-designed. The consequence of the incident could have been much higher, if the hydrogen would have cumulated in the semi-confined structure neighbouring the trailers.
This could be an example of neglecting basic safety engineering principles to abate cost.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Release pressure [MPa]
7.5
Probable IGNITION SOURCE

References

Sources categories
Investigation report
Reference & weblink

Investigation Report on the "7-30" General Leakage and Fire Accident at Dongguan Juzhengyuan Technology Company Limited, Lixia Island, Shatian Town, Dongguan City.

B.Wang et al., Hydrogen related accidents and lesson learned from events reported in the
in east continental Asia,#2023, ICHS-2023