An explosion in a sulphonation plant

Event

Event ID
982
Quality
Description

The incident occurred in an electrostatic filtration unit of a sulphonation plant. When flushing with air during the start-up phase, an explosion occurred in the upper part of the plant, at the electrostatic precipitators. The most serious effects of the pressure wave were the violent detachment of the manhole cover of the plant, the rupture of two insulating supports and the deformation of the gas distributor plate.

[DECHEMA]

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
Germany
Date
Component involved
reactor / oven / furnace / test chamber
Failure mode
rupture & ignition
Initiating cause
accidental hydrogen entrance
Root CAUSE analysis

The INITIATING CAUSE was the formation of an explosive atmosphere containing hydrogen.

Moisture-bearing and corrosive gases entered the electrostatic filtration plant during the start-up phase and during operation.
Air from an air dryer is used for cleaning, to prevent deposition of corrosive and conductive moisture on the thermo-protective insulation of the upper part of the filtration plant and lines. Hydrogen was probably generated in the converter, in the inlet moisture separator and/or in the acid scrubber (absorber) by the reaction of iron with sulphuric acid.
The ignition source of the hydrogen / air mixture were electrical discharges observed in the ESP.

This suggests a ROOT CAUSE related to poor control of the process parameters and to design shortcoming.

Root causes
Date entry in HIAD
01/01/2024

Facility

Application
Chemical industry
Sub-application
Inorganic chemicals products
Hydrogen supply chain stage
All components affected

sulphonation plant, manhole, electrostatic precipatators

Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

At the moment of the incident, the sulphonation plant was starting -up and flushed with air. It is probable that this start-up was part of the production cycle, to clean the system.

Description of the facility/unit/process/substances

In organic chemistry, aromatic sulfonation is a reaction in which a hydrogen atom on an arene is replaced by a sulfonic acid (−SO2OH) group. Together with nitration and chlorination, aromatic sulfonation is a widely used electrophilic aromatic substitutions. Aryl sulfonic acids are used as detergents, dye, and drugs.
Typical conditions involve heating the aromatic compound with sulfuric acid:
C6H6 + H2SO4 → C6H5SO3H + H2O

The report of this event does not specify the products of this plant/unit.
Wikipedia mentions among applications surfactants, detergents, dyes, and pharmaceuticals.

[Wikipedia https://en.wikipedia.org/wiki/Aromatic_sulfonation ]

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0

Lesson Learnt

Lesson Learnt

According to the ProcessNet database [DECHEMA event no. 05/ 2001], the handling of sulphuric acid in the presence of certain metals, e.g. iron and moisture, can produce hydrogen. If the hydrogen is allowed to accumulate, it can form potentially explosive hydrogen / air mixtures with a very low ignition energy. In the specific case of the electrostatic filtration plant, it is necessary to ensure that the hydrogen concentrations remains below the explosive limit before starting up the plant. The flushing has to be performed for a sufficiently long time and its effectiveness confirmed by concentration measurements.
A typical reaction is: Fe (s) + H2SO4 (aq) → FeSO4 (aq) + H2 (g)

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2,
moisture
Probable IGNITION SOURCE
Explosion type

References

Sources categories
DECHEMA
Reference & weblink

Event description 05/2001 of the Dechema database www.dechema.de/EreignisDB