The incident occurred during delivery of a bundle of 28 cylinders to a metal manufacturing company. A hydrogen leak occurred due to due to a wrong operation of the the truck crane. While loading an empty bundle, the piping of a full cylinder was hit, casuing the leak.
Since the release could not be stopped by intervening at the leaking point, the fire brigade decided to vent the whole content of the pallet (246 m3) by gradually opening the valves and by keeping the rack cool.The rack of the bottles was empty after four hours and the rescue operation ends at noon after the cylinder rack has been checked by an expert from the gas supply company. The residents returned to their homes and the plant's activity restarted one hour later.
- Event Initiating system
- Classification of the physical effects
- Unignited Hydrogen Release
- Nature of the consequences
- leak no ignition
- Macro-region
- Europe
- Country
- France
- Date
- Component involved
- piping (collector)
- Failure mode
- rupture, no ignition
- Initiating cause
- impact, rollover, crash
- Root CAUSE analysis
The INITIATING cause was the mechanical damage of one of the compressed hydrogen cylinders, by an erroneous manoeuvring of the operator .
The ROOT CAUSE had two components a manoeuvre error and an inadequate safety design of the load. it should be possible to isolate the individual cylinders of the pallet before shipping, to minimise the hazard related to a leak on one of them.
- Root causes
- Date entry in HIAD
- 01/01/2018
Facility
- Application
- Hydrogen transport and distribution
- Sub-application
- CGH2 cylinders truck
- Hydrogen supply chain stage
- All components affected
cylinders
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Process pressure range [MPa]
- medium to high pressure (10 to 50 MPa)
- Location type
- Open
- Location
- industrial area
- Operational condition
- Pre-event occurrences
The accident took place when replacing the empty cylinders with full ones.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Post-event summary
No consequence.
- Emergency action
Since the leak could not be stopped locally, The fire brigade decided to drain the whole content of the pallet (246 m3) by gradually opening the valves and by keeping the rack cool.
The rack of the bottles was empty after four hours and the rescue operation ends at noon after the cylinder rack has been checked by an expert from the gas supply company. The residents returned to their homes and the plant's activity restarted one hour later.
- Emergency evaluation
A specialized expert emergency support cell estimated the leakage rate at 0.48 kg/s. They also estimated the distance to the Low flammability limit (LFL) about 30 m and the effects of an explosion in the event of delayed ignition of the cloud in the open air at 50 and 20 mbar over-pressure, for respectively 80 and 130 m.
Lesson Learnt
- Lesson Learnt
The ARIA report (see references) does not mention any corrective action following the incident, but improved (safer) loading/unloading procedure would certainly be required.
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Released amount (kg)
- 21
- Release temperature [°C]
- 25
- Release pressure [MPa]
- 20
- Probable IGNITION SOURCE
References
- Sources categories
- ARIA
- Reference & weblink
Event description in the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/35405/
(accessed October 2020)