Jet fire of coke gas in a steel industry

Event

Event ID
937
Quality
Description

The fire took place during maintenance works in one out of the three gas extractors of the coke process line. Main cause was the displacement of a flange which allowed the entrance of flammable mixture gas (methane, carbon monoxide hydrogen and benzene) which ignited probably due to electrostatic spark.
According to the ARIA report total quantity of gas released was 62 400 m³, consisting of 11,7 t CH4, 0,98 t C6H6, 5,1 t CO and 3,4 t H2.

During maintenance works, gas extractors were usually isolated and kept under continuous flow of N2. However, in this case, N2 pressure seemed to be not enough to avoid the entrance of flammable gas.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
France
Date
Component involved
valve (generic)
Failure mode
rupture & ignition
Initiating cause
inadequate or no purge
Root CAUSE analysis

INITIATING cause was probably the inert gas pressure insufficient to prevent the entrance of the flammable mixture.

Root causes
Date entry in HIAD
01/01/2018

Facility

Application
Steel and metals industry
Sub-application
Steel metallurgy
Hydrogen supply chain stage
All components affected

coke process line, flange

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
unknown
Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

The event took place during maintenance of a gas extractor, which has a diameter of 1400 mm. During maintenance, the line was isolated from gas stream using two flanges, one before and another one after the equipment.
The accident occurred after maintenance works have finished and the gas extractor was been prepared again for operation: the procedure required as final steps the closing of the downstream flange and then the opening of the inlet one. The leak occurred immediately after the opening of the inlet flange.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
2
Post-event summary

Damage to property: on-site more than 2 millions of Euros, off-site more than 0.5M millions of Euros. The released susbtances were:
H2 3.4 t
CO 5.1 t
CH4 11.7 t
C6H6 0.98 t

Emergency action

The employers have been evacuated. The site fire brigade put the extractor under nitrogen and cooled it by water jets. The fire and the leak are stopped after approximately 1 hour.

Lesson Learnt

Corrective Measures

The operator has foreseen to improve the procedure for the isolation of the section at the following maintenance and to review the risk assessment.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2 3.4 t
CO 5.1 t
CH4 11.7 t
C6H6 0.98 t
Released amount (kg)
3400000
Probable IGNITION SOURCE

References

Sources categories
eMARS
Reference & weblink

Event description in the European database eMARS
https://emars.jrc.ec.europa.eu/en/eMARS/accident/view/2c958f15-e9a3-11e…
(accessed September 2020)

Online news Le Port de Saint Louis: company communication

ARIA incident No. 1706