Skip to main content
Clean Hydrogen Partnership

Release from a hydrogen pipeline

Event

Event ID
933
Quality
Description

During maintenance work on a gas pipeline carrying hydrogen , a worker hears a leak at a bridge. The operator measures an concentration of 3% of the low flammability limit at few centimetres from the leak, and no detection beyond 25 cm. The area was highly ventilated. The technicians secured the area, isolated the section five hours later and started the controlled gas release. after two additional hours the pressure had reduced to zero and they started the nitrogen inerting. The pipe was repaired the next day.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
Europe
Country
France
Date
Component involved
pipeline (generic)
Failure mode
rupture, no ignition
Initiating cause
unknown
Root causes
Unknown
Date entry in HIAD
01/01/2018

Facility

Application
Hydrogen transport and distribution
Sub-application
Pipeline
Hydrogen supply chain stage
All components affected

hydrogen pipeline, 80 mm diameter, 75 bar pressure

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium pressure (2 to 10 MPa)
Location type
Open
Location
countryside or desert
Operational condition
Pre-event occurrences

The begin of the leak was unknown. The leak was detected during maintenance work, what does not mean that it started at that moment.
The pipeline section (diamater DN80) dated back to 1988.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Emergency action

14.30 detection of the leak. Area secured,
19:15 Isolation of the pipeline section
20:00 Start controlled emptying
23:00 Pipeline pressure at zero, start of nitrogen injection
Day after: repair of the leak

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Release pressure [MPa]
7.5
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

Event description in the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/43705/
(accessed September 2020)