Ignited hydrogen leak at an aerospace testing facility

Event

Event ID
918
Quality
Description

The event occurred in a university research building dedicated to the study of the take-off of space launchers. During the hydrogen pressure pre-setting phase, a flame developed at a pressure regulator on the line located on the walkway above the test hall.

Operators gave the alarm, based on video surveillance images. They closed the supply line and started to purge the system.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
France
Date
Component involved
pressure regulator
Failure mode
rupture & ignition
Initiating cause
unknown
Root CAUSE analysis

The INITIATING CAUSE was a combination of two technical failures:
- A hydrogen leak on the pressure regulator (technical cause unknown).
- An electrical short circuit on one of the equipment in the environment near the regulator.
The latter was caused either by a material defective of a system temporarily installed on the bridge for experimentation, either by over-voltage due to accumulation of moisture in one of the elements of the electrical circuit following a water leak the day before.

The ROOT CAUSE is unknown.

Root causes
Unknown
Date entry in HIAD
01/01/2018

Facility

Application
Laboratory / R&D
Sub-application
Aerospace
Hydrogen supply chain stage
All components affected

experimental testing laboratory, pressure reducer device

Location type
Semiconfined
Location
populated area
Operational condition
Pre-event occurrences

The event occurred during the starting of a test, in the hydrogen pressure pre-setting phase

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

No injury and damage.

Emergency action

The alarm was given by an operator. On-site officers contained the fire.

Lesson Learnt

Lesson Learnt

Probably better procedures for adequate monitoring/control of materials and equipment will reduce probability of occurrence of this type of incident.

Corrective Measures

According to the ARIA report, the operator is implementing the following measures to be able to restart the testing campaign:
1. Replacement of the electrical connection potentially causing the short circuit, as well as electrical cables damaged by the fire;
2. Displacement of the system potentially causing the short circuit, in an area far from the hydrogen line;
3. Partial restart of the control-command console, aiming at leak tests and verification of the absence of short circuit;
4. Replacement of the valves, seals of the defective hydrogen pressure regulator and check of the other pressure regulators and pressure sensors;
5. Leak-test of the line, first under nitrogen and then under hydrogen;
6. Re-powering of the entire control panel for functional tests of the combustion chamber, first at low flow rates of hydrogen, then at nominal flow rate.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE
Flame type

References

Sources categories
ARIA
Reference & weblink

Event 51294 of the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/51294/
(accessed September 2020)