Fire in a chlorine electrolysis plant

Event

Event ID
917
Quality
Description

The event affected a chlor-alkali electrolysis plant shutdown and under maintenance (SEVESO upper tiers). First an explosion and then a fire occurred on the condensate pipe of the electrolyser. Flames escape from the end of the pipe and spilled into a 75 m³ open sky tank, containing the electrolysis products (water, HCL, NaOH, Na).

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Component involved
electrolytic cell
Failure mode
rupture & ignition
Initiating cause
inadequate or wrong design
Root CAUSE analysis

INITIATING CAUSE was the formation and ignition of a flammable mixture at the outlet of this pipe.
IGNITION SOURCE was a spark related to the work on the furnace.

According to the ARIA report, a design error was the cause of the incident. The overflow of the hydrogen safeguard, consisting in a hydraulic system, ad been erroneously connected to the condensate piping.
Due to the fact that the HCl furnace was in maintenance, an excess of hydrogen under overpressure formed and escaped through the condensate piping.
This area had not been identified as ATEX zone during work on the furnace, because hydrogen was not expected to be present in the area.

Therefore, the ROOT CAUSE was a wrong design. Moreover, work permits and related assignment of temporary ATEX zone should have followed stricter criteria and a more effective risk assessment.

Root causes
Date entry in HIAD
01/01/2018

Facility

Application
Chemical industry
Sub-application
Chlorine production
Hydrogen supply chain stage
All components affected

condensate piping

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Location type
Open
Location
industrial area
Operational condition
Pre-event occurrences

The electrolysis plant was normally function, maintenance works started nearby

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

The storage of epoxy is destroyed et three plastic pipelines are burned. The electrolysis unit is stopped for 24 ore.

Emergency action

14:25 Immediately after the explosion, the staff started the fighting of the fire by means of fire-hoses.
14:30 The fire brigade arrived and cooled the platform where the furnace was located.
15:00 Observing that the fire gains intensity when reducing the cooling effect of the water, the operator decided to stop the production and the fire stopped.
Due tot possible presence of invisible flame, the fire brigade carries out a control by thermal camera on the various pipes overhanging the tank being exposed to thermal radiation, and leave at 16:00

Lesson Learnt

Corrective Measures

According to the ARIA report, the operator implemented the following actions:

1. modifications to allow the independent discharge to the atmosphere of the surplus of hydrogen.
2. assessment of the electrical equipment of the area.
3. Verification of the installation modifications history
4. Review of the HAZOP (Hazard and Operation Procedures) of the circuits of hydrogen, chlorine and hydrochloric acid .
5. Control of the hydrogen detection system of the electrolytic unit

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE
Explosion type
Detonation
Flame type

References

Sources categories
ARIA
Reference & weblink

Event 52072 of the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/52072/
(accessed September 2020)