Fire of a mixture of hydrogen and hydrocarbons in a refinery

Event

Event ID
895
Quality
Description

The fire occurred on the tube plate gaskets of 3 of the 4 exchangers loaded with catalytic reforming effluent. The fuel (500°C and p=30 bar) was a mixture of 30% hydrocarbons and 70% hydrogen.

After depressurisation of the unit and nitrogen flushing (some problems to access the valves), the exchangers being cooled (overall flow 600 m³/h on 3 units), the fire was controlled until extinction by nitrogen injection.

The accident was apparently due to incorrect tightening of the threaded rods; only 1/5 were correctly tightened on one of the heat exchangers involved. Three threaded rods break and the gasket surfaces were poorly prepared.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
France
Date
Component involved
heat exchanger (flange)
Failure mode
rupture & ignition
Initiating cause
loss of tightness (wrong operation)
Root CAUSE analysis

The INITIATING cause was the release of hydrogen at a flange.
The ROOT (or INTERMEDIATE) cause was the wrong execution of the flange joint (incorrect tightening, bad quality of the gasket surface)

Root causes
Date entry in HIAD
01/01/2018

Facility

Application
Petrochemical industry
Sub-application
Catalytic reforming processes
Hydrogen supply chain stage
All components affected

heat exchanger of the catalytic reforming unit

Process temperature range [C]
Very high temperature (500°C to 1000°C)
Location type
Open
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

The tightening procedure is reviewed (hot tightening procedure: 340 °C and 8 bar) before the
charge is introduced again.

Emergency action

The unit was depressurised, nitrogen flushed (with some problems to access the valves), the exchangers being cooled (overall flow 600 m³/h on 3 units), the fire was controlled until extinction by nitrogen injection.

Lesson Learnt

Corrective Measures

The flange tightening process was reviewed and improved.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2 70%
hydrocarbons 30%
Release temperature [°C]
500
Probable IGNITION SOURCE

References

Sources categories
ARIA
Reference & weblink

Event description in the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/26616/
(accessed September 2020)