Fire at a hydrogen storage of a nuclear power plant

Event

Event ID
890
Quality
Description

The accident took place when replacing a pallet of empty hydrogen cylinders with a new full one. The pallet in service (almost empty) was not disconnected from the gas supply line. When the operator in charge of handling (fork lift) begun to remove the pallet in service from its position, he teared off the hose connecting it to the pressure relief system. The pressurised hydrogen in the pipes and in the pallet escaped and ignited.

The intervention of the teams from the plant and external emergency services extinguished the fire in 1h45.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Component involved
hose (generic)
Failure mode
rupture & ignition
Initiating cause
wrong operation
Root CAUSE analysis

The INITIATING CAUSE a wrong application of the procedure for replacing gas cylinders, which brought to the tearing and rupture of the connection hose.
There were however several contributing causes (uncontrolled access to the storage area, non respecting of the ATEX distance for welding work, abnormally high frequency to replace the gas pallets, etc.).
The ROOT CAUSE lies therefore in the lack of adaptation of the safety operation to the temporary different working conditions.

Root causes
Date entry in HIAD
01/01/2018

Facility

Application
Power plant
Sub-application
Nuclear power plant
Hydrogen supply chain stage
All components affected

hydrogen cylinders pallet

Location type
Open
Location
industrial area
Operational condition
Pre-event occurrences

A leak of hydrogen at the alternator required a temporary increased rate of hydrogen supply. Therefore the pallets had to be changed much more frequently.
Other maintenance work (including welding) was ongoing, and as a consequence the pallet storage location was open. The external company worker coming to change the pallet was able to access the storage without asking someone from the plant.

Description of the facility/unit/process/substances

DESCRIPTION OF THE FACILITY
The storage consisted in 5 hydrogen pallets of 10 cylinders each of and 2 nitrogen pallets with 10 each. All the cylinders were of 50 l with 200 bar compressed gas.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
2
Post-event summary

One worker was injured because he fell when flying the location. The other due to a post-event shock.

Emergency action

the fire brigades controlled the fire by cooling the gas cylinders. The fire was extinguished in 1h45.

Lesson Learnt

Lesson Learnt

The ASN (National Safety Authority) performed an investigation and concluded that:
1- Many procedures were disregarded, including communications of the ongoing operations and the temporary changes
2- A reduction of the number of workers in teams, without correspondingly assessment of the consequences
3- A lack of related risk assessment
4- ATEX-compatible tools were not used in the zones (Forklift and welding material were inside the ATEX zone 2).

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE
Explosion type

References

Sources categories
ASN
Reference & weblink

National Safety Authority request of action following the inspection (in French)

Local newspaper online news of 15th April 2020