Release from the dispenser of a refuelling station

Event

Event ID
803
Quality
Description

The vent occurred at a hydrogen refuelling station (HRS) of a research laboratory (not public) serving heavy- and light-duty vehicle. The affected dispenser was a 700-bar dispenser for light-duty use supplied by an on-site gaseous storage of approx. 600 kg.
The leak occurred due O-ring extrusion and/or failure, on a medium-pressure manual isolation ball valve (normally open). The valve was connected to the end plug of a medium pressure tank. The failure of an O-ring created an external leak which could not be isolated.
The released quantity were small, in the 1 to 2 kg range. The leak was audible, but the hydrogen did not ignite and activated a safety sensor.
This leak occurred during the recommissioning of the medium pressure system following extended downtime and rebuild of a system that had been originally installed at a different facility.

Event Initiating system
Classification of the physical effects
No Hydrogen Release
Nature of the consequences
Macro-region
North America
Country
United States
Date
Component involved
dispenser (gasket)
Failure mode
leak, no ignition
Initiating cause
material degradation (ageing)
Root CAUSE analysis

The INITIATING CAUSE was the failure of a O-ring.
The ROOT CAUSE is related not only to a material failure, but also to the fact that the event occurred at the recommissioning of the medium pressure system, originally installed at a different facility, and after extended downtime. Ageing may have played a role in this case.

Root causes
Date entry in HIAD
30/08/2024

Facility

Application
Hydrogen refuelling station
Sub-application
HRS 70 MPa
Hydrogen supply chain stage
All components affected

dispenser, valve, o-ring

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
high pressure (above 50 MPa)
Location type
Open
Location
populated area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Property loss (onsite)
0
Post-event summary

This is a near-miss

Emergency action

Probably just an automatic shut down

Lesson Learnt

Lesson Learnt

The safety system worked as expected.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Release pressure [MPa]
70
Probable IGNITION SOURCE

References

Sources categories
Scientific article
Reference & weblink

A. Al-Douri et al., Populating the Hydrogen Component Reliability Database (HyCReD) with Incident Data from Hydrogen Dispensing, paper ID232, Proceedings of ICHS 2023
https://hysafe.info/uploads/papers/2023/232.pdf
(accessed August 2024)

A detailed analysis was presented by Clark et al. at the 2024 Center for Hydrogen Safety Americas Conference
The resentation is behind a paywall, but the abstract is available on line:
https://proceedings.aiche.org/conferences/center-hydrogen-safety-confer…
(accessed January 2025)