Release from the dispenser of a refuelling station

Event

Event ID
803
Quality
Description

The vent occurred at a hydrogen refuelling station (HRS) of a research laboratory (not public) serving heavy- and light-duty vehicle. The affected dispenser was a 700-bar dispenser for light-duty use supplied by an on-site gaseous storage of approx. 600 kg.

The leak occurred due O-ring extrusion and/or failure, on a medium-pressure manual isolation ball valve (normally open). The valve was connected to the end plug of a medium pressure tank. The failure of an O-ring created an external leak which could not be isolated.

The released quantity were small, in the 1 to 2 kg range. The leak was audible, but the hydrogen did not ignite and activated a safety sensor.

This leak occurred during the recommissioning of the medium pressure system following extended downtime and rebuild of a system that had been originally installed at a different facility.

Event Initiating system
Classification of the physical effects
No Hydrogen Release
Nature of the consequences
Macro-region
North America
Country
United States
Date
Component involved
dispenser (gasket)
Failure mode
leak
Initiating cause
material degradation (ageing)
Root CAUSE analysis

The INITIATING CAUSE was the failure of a O-ring.

The ROOT CAUSE is related not only to a material failure, but also to the fact that the event occurred at the recommissioning of the medium pressure system, originally installed at a different facility, and after extended downtime. Ageing may have played a role in this case.

Root causes
Date entry in HIAD
30/08/2024

Facility

Application
Hydrogen refuelling station
Sub-application
HRS 70 MPa
Hydrogen supply chain stage
All components affected

H2 dispenser

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
high pressure (above 50 MPa)
Location type
Open
Location
populated area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Property loss (onsite)
0
Post-event summary

This is a near-miss

Emergency action

Probably just an automatic shut down

Lesson Learnt

Lesson Learnt

The safety system worked as expected.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Release pressure [MPa]
70
Probable IGNITION SOURCE

References

Sources categories
Scientific article
Reference & weblink

A. Al-Douri et al., Populating the Hydrogen Component Reliability Database (HyCReD) with Incident Data from Hydrogen Dispensing, paper ID232, Proceedings of ICHS 2023

https://hysafe.info/uploads/papers/2023/232.pdf

(accessed August 2024)

A detailed analysis was presented by Clark et al. at the 2024 Center for Hydrogen Safety Americas Conference

The resentation is behind a paywall, but the abstract is available on line:

https://proceedings.aiche.org/conferences/center-hydrogen-safety-confer…

(accessed January 2025)