Event
- Event ID
- 748
- Quality
- Description
Employees were refilling a rack of 15 hydrogen cylinders that were connected together on a steel pallet with railings.
A leak developed at a valve and the pressurized hydrogen ignited. Operations activated a deluge sprinkler system, which turned off the compressor that was pumping in hydrogen.
The fire was contained by the sprinkler system as the hydrogen pressure bled off.There were no injuries.
- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- fire
- Macro-region
- North America
- Country
- United States
- Date
- Component involved
- valve (generic)
- Failure mode
- leak & ignition
- Initiating cause
- unknown
- Root causes
- Unknown
- Date entry in HIAD
- 01/01/2020
Facility
- Application
- Hydrogen stationary storage
- Sub-application
- GH2 storage
- Hydrogen supply chain stage
- All components affected
hydrogen cylinders, rack, compressor, sprinkler
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Location type
- Unknown
- Location
- populated area
- Operational condition
- Pre-event occurrences
A leak developed at a valve of a hydrogen cylinder during filling. It is assumed that this action was part of the normal operation.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Emergency action
The activation of the safety deluge sprinkler system turned off the hydrogen compressor and contained the fire till the hydrogen pressure bled off.
Lesson Learnt
- Lesson Learnt
A plausible, logic generic is the need of proper inspection and maintenance, and the regular improvement of the related procedure.
In similar accidents, one of the recommendations was the installation of control valve on each of the cylinders in the rack. However, in this case it seems that the accidents occurred when filling the cylinders, and the description does not clarify where he hydrogen feeding the fire was coming from: from the cylinders of form the compressor of from both?
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Release temperature [°C]
- 25
- Probable IGNITION SOURCE
References
- Sources categories
- OHSA
- Reference & weblink
OHSA report 0951510
https://www.osha.gov/pls/imis/establishment.inspection_detail?id=103880…