Event

Event ID
735
Quality
Description

The incident occurred at the recycle hydrogen compressor of a hydrodesulphurisation unit. The compressor was equipped with a suction rectifier. The drainpipe of this rectifier had been corroded internally by a combination of hydrogen sulphide and ammonia residues. The corrosion produced a 2mm wide x 90mm long hole, through which hydrogen escaped. The process condition (45C and 3.7Mpa) had created the conditions for the corrosion to take place, including presence of steam. The drainage piping had a horizontal section of approximately 10 m, with an upward outlet. This upward outlet made it impossible to drain out completely the pipe. "
The leak was detected thanks to an abnormal noise was heard in the operator cabin. The workers checking the site detected the smell of hydrogen sulphide, upon which the plant operator gave the order to shut down the operation immediately.

[Note of the HIAD validator: the original data in the database RISCAD reported the development of a fire. The KHK database mentions only a leak].

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
Asia
Country
Japan
Date
Component involved
compressor / booster / pump (pipe)
Failure mode
leak, no ignition
Initiating cause
material degradation (internal corrosion / erosion)
Root CAUSE analysis

The INITIATING CAUSE was internal corrosion leading to a pipe opening.
The ROOT CAUSE was a design of the drainpipe which could not be fully drained.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Petrochemical industry
Sub-application
Hydrodesulphurisation process
Hydrogen supply chain stage
All components affected

pipe, recycle hydrogen compressor,

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium pressure (2 to 10 MPa)
Location type
Open
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0

In-depth data

Release type
gas
Involved substances (% vol)
H2,
H2S (impurities)
Release temperature [°C]
45
Release pressure [MPa]
3.7
Probable IGNITION SOURCE

References

Sources categories
KHK
Reference & weblink

High Pressure Gas Accident Cases Database of the KHK (High Pressure Gas Safety Association):
https://www.khk.or.jp/public_information/incident_investigation/hpg_inc…
(accessed May 2025)

The first entry in HIAD was comingfrom RISCAD, which is now closed.