Explosion at a hydrogen furnace

Event

Event ID
718
Quality
Description

Two employees were working on a electric furnace under hydrogen atmosphere that had jammed. The furnace exploded. The employees sustained flash burns to their faces and were taken to the hospital, where they were treated and released later the same day.
The furnace had not been purged for 10 hours, as required by the manufacturer.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
North America
Country
United States
Date
Component involved
reactor / oven / furnace / test chamber
Failure mode
internal explosion
Initiating cause
inadequate or no purge
Root CAUSE analysis

The workers were using a retrieval tool not suitable for servicing a hydrogen furnace. This may have been the IGNITION SOURCE for the explosion.
The furnace had not been purged for 10 hours, as required by the manufacturer.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Chemical industry
Sub-application
unspecified chemical process
Hydrogen supply chain stage
All components affected

Hydrogen furnace

Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

The furnace had not been purged for 10 hours, as required by the manufacturer. The retrieval tool the workers were using was not suitable for servicing a hydrogen furnace, and may have been the ignition source for the explosion.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
2
Post-event summary

They sustained flash burns to their faces and were taken to the emergency room at Petaluma Valley Hospital, where they were treated and released later the same day.

Lesson Learnt

Lesson Learnt

This is a case of incident caused by failing to follow existing procedures. Furnace operation, even in case of repairs, should strictly follow manufacturer's requirements. In particular, in presence of hydrogen in the system, effective purging is a critical step.
Care should be taken in selecting retrieval tool avoiding them acting as ignition source.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE
Explosion type
Deflagration

References

Sources categories
OHSA
Reference & weblink

U.S. Department of Labor Occupational Safety & Health Administration OHSA incident report:
https://www.osha.gov/ords/imis/accidentsearch.accident_detail?id=170764…