Fire on a hydrotreater of a refinery

Event

Event ID
677
Quality
Description

The incident occurred at an oil refinery hydrotreater used to de-sulphurise naphtha. A small leak developed in one of the finned tubes of the heater pre-heating the naphtha-hydrogen mixture before the reactor. The leak resulted in a 0.6 m long torch flame noticed by an employee. The hydrotreater was then shut down by cutting off the flow of naphtha and the flow of fuel to the burners in the heater. The hydrogen flow was maintained to cool and sweep the reactor during the shutdown operation.

The torch flame appeared to diminish significantly while only the hydrogen was flowing. However, molten metal dripping from the heater indicated that a much more severe fire was still in progress. The fire was eventually controlled by reducing the hydrogen flow and injecting steam into the heater. The fire caused significant damage to several tubes.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
North America
Country
United States
Date
Component involved
heat exchanger (pipe)
Failure mode
leak & ignition
Initiating cause
material degradation (generic)
Root CAUSE analysis

The INITIATING CAUSE was the cracking of a tube, with release and ignition of a hydrogen-naphtha mixture.
The measure taken to fight the emergency were effective in (1) reducing the amount of total flammable substance, and (2) avoiding the further damage to the heater due to further hating with reduced flow in the tubes of the heat exchanger. However, the plant operator failed to assess properly the severity of the flame and to avoid continued damage of the hydrogen flame.

Root causes
Date entry in HIAD
28/01/2026

Facility

Application
Petrochemical industry
Sub-application
naphtha catalityic reformer
Hydrogen supply chain stage
All components affected

heater, heat exchanger tubes

Location type
Semiconfined
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
US$
Property loss (onsite)
12.500.000
Post-event summary

. Inspection of the damaged heater revealed that the fire had completely melted 3.5 m long sections of 32 finned tubes.

Emergency action

The flame was estinguished after cutting off the process gas flows (both naphtha's and hydrogen's) and stpping the fuel to the fired heater.

Lesson Learnt

Lesson Learnt

The event showed that naked eye observation of hydrogen flame does not provide a reliable assessment of the severity of the incident. This and other early cases, such as those reported by NASA (Ordin, 1974) brought later to the adoption of more sophisticated inspection tool, such as infrared cameras.

In-depth data

Probable IGNITION SOURCE

References

Sources categories
Zalosh
Reference & weblink

Reported at Section 2.1 of Zalosh and Short report:
COMPARATIVE ANALYSIS OF HYDROGEN FIRE AND EXPLOSION INCIDENTS
Quarterly Report No. 2 for Period December 1, 1977 - February 28, 1978
https://www.osti.gov/biblio/6566131
(accessed September 2020)

Also in H2TOOLS
https://h2tools.org/lessons/naphtha-hydrotreater-fire
(accessed January 2026)