Hydrogen compressor explosion and fire at a refinery.

Event

Event ID
675
Quality
Description

An explosion and fire occurred at a reciprocating recycle hydrogen compressor during commissioning of a new Diesel hydrotreatement Unit. It happened during the reactor pre-sulphidisation step, when the recycle gas contained 9000 ppm of H2S (hydrogen sulphide) and the pressure was at 940 psig (65 bar).
The failure of retaining bolts on head-end suction valve unloader of recycle cylinder on compressor allowed release of process gas.

The compressor was damaged.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
North America
Country
United States
Date
Component involved
compressor / booster / pump (valve)
Failure mode
rupture & ignition
Initiating cause
material degradation (stress-corrosion)
Root CAUSE analysis

The INITIATING CAUSE was the failure of valve bolts on the hydrogen compressor which recycles the H2S-containing hydrogen coming from the hydrotreater.
Investigations revealed that the bolts failed due to material inappropriate to prevent sulphide stress cracking) and inadequate design for the service. The manufacturer did not comply with the company's practice for reciprocating compressors in H2S applications.

Therefore, the ROOT CAUSE was the choice of incorrect material for the components of the valve, as delivered by the manufacturer. This mishap was not noticed/identified by the plant operators.

Root causes
Date entry in HIAD
01/01/2021

Facility

Application
Petrochemical industry
Sub-application
Hydrodesulphurisation process
Hydrogen supply chain stage
All components affected

hydrogen recycling compressor, bolts

Location type
Confined
Location
industrial area
Operational condition
Description of the facility/unit/process/substances

DESCRIPTION OF THE PROCESS
A Diesel Hydrotreater Unit removes impurities like sulphur and nitrogen from diesel, in the presence of a catalyst and hydrogen.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
US$
Property loss (onsite)
100.000
Post-event summary

Damage to equipment US $100 000 (1993).
Damage to compressor shelter, instrumentation. Estimated 250 man hours spent on investigation.

Lesson Learnt

Lesson Learnt

The ICHEME database (see reference) lists the following lesson learnt:
(1) Standards are essential to the safety of any process plant project. These standards apply to design control, purchasing, construction, and inspection and testing of purchased equipment.
(2) Each group involved in a project, whether contractors, suppliers, designers, procurement, manufacture, construction, etc. plays a key role in assuring the equipment's fitness for use.
(3) All possible process conditions must be detailed in the specification for the purchase of equipment.
(4) HAZOP studies must include all deviations from the design operating conditions such as shutdown, start-up, maintenance, and other activities such as the pre-sulphiding process to check the adequacy of the design.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE
Explosion type

References

Sources categories
ICHEME
Reference & weblink

Event description extracted from the UK database ICHEME in PDF

https://www.icheme.org/media/7178/activity-operationalactivities-detail…
(accessed November 2020)