Skip to main content
Clean Hydrogen Partnership

Fire on a gas heater pipe

Event

Event ID
565
Quality
Description

Failure of an 8 inch steel outlet pipe from a gas heater which ruptured and allowed hydrogen to escape with ensuing rapid ignition.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
Bosnia and Herzegovina
Date
Component involved
heat exchanger (pipe)
Failure mode
internal explosion
Initiating cause
material degradation (generic)
Root causes
Unknown
Date entry in HIAD
01/01/2020

Facility

Application
Petrochemical industry
Sub-application
Unspecified refinery process
Hydrogen supply chain stage
All components affected

gas heater outlet pipe

Location type
Unknown
Location
populated area
Operational condition
UNKNOWN

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0

Lesson Learnt

Lesson Learnt

Rupture of hydrogen or process gases tubes in pre-heaters /heat-exchangers / fired heaters is a recurrent event up to recent times. This is not surprising, considering the high temperatures and pressures involved. The most common causes are materials degradations due to manufacturing defects and operative stresses. Ruptures tend to happen during operative transients, which may cause over-heating due to reduction of flows. When the releases occur also in presence of naked flames, as in fired heaters, which use conventional fuels burners, ignition and explosion in the confined of the heater box is ensured. Nevertheless, due to sturdy heater constructions, it rarely happens that damage extends to the outside environment.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE

References

Sources categories
ICHEME
Reference & weblink

Event nr 3300 of the UK database ICHEME in PDF format
https://www.icheme.org/knowledge/safety-centre/resources/accident-data/