Fire in a hydrogen pipe

Event

Event ID
546
Quality
Description

A leak occurred on a 4 inch hydrogen main gas line which ran along a pipe bridge at the east end of a first stage compression plant building. The relased hydrogen ignited.
The source of ignition was hot welding sparks arising from work being carried out by contract personnel whilst installing a new chlorine line above the hydrogen lineon the pipe-bridge.

Before the welding work was carried out, an explosivity test had been carried out in the area and a 0 explosive gas result had been reproted in the work permit.
An investigation into the incident found that the removed section of the hydrogen main revealed an elliptical hole 2 centimetres x 1 and a half centimetres. It was only when the lagging was disturbed that the hydrogen leak became obvious.The area around the hole in hydrogen main was very pitted suggesting that the failure was due to localised corrosion.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
United Kingdom
Date
Component involved
pipe (generic)
Failure mode
leak & ignition
Initiating cause
wrong operation
Root CAUSE analysis

The INITIATING CAUSE was an elliptical hole of 2 centimetres x 1.5 centimetres.
It was very probably due to localised corrosion.
The leak was not detected during the explosivity test because of a build up of scale sealing the hole, possibly dislodged later by the activities of the contractors in the area. The technical reason for the corrosion is not provided or known.
Neverhtless, ROOT CAUSE could be possibly attributed to a lack of effective inspection, not able to detect the progress of the corrosion.

Root causes
Date entry in HIAD
01/01/2020

Facility

Application
Chemical industry
Sub-application
Hydrodesulphurisation process
Hydrogen supply chain stage
All components affected

Separation equipment

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
ambient pressure (around 0.1 MPa)
Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

Welding works were ongoing, but the plant had not been shutdown (pesene of flammabe gases had been excluded by measures).

Emergency & Consequences

Number of fatalities
unknown
Number of injured persons
unknown
Emergency action

The welder saw the hole appeared as if the lagging on the pipe had caught fire and an unsuccessful attempt was made to put it out using carbon dioxide fire extinguishers and then water.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE
Flame type

References

Sources categories
ICHEME
Reference & weblink