Event
- Event ID
- 497
- Quality
- Description
At the workshop of a linear accelerator site, a hydrogen retort used for brazing exploded due to the ignition of a flammable mixture of hydrogen and air.
The explosion propelled the retort shell to the roof of the brazing area and then back to the floor. It causes two injuries.
- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- North America
- Country
- United States
- Date
- Component involved
- reactor / oven / furnace / test chamber
- Failure mode
- internal explosion
- Initiating cause
- inadequate or no purge
- Root CAUSE analysis
The INITIATING CAUSE was the accidental formation and ignition of a flammable air-hydrogen mixture in the retort.
The post-accident inspection did not identify any mechanical or physical malfunctioning of the equipment. The preparatory procedure foresaw (1) to vacuum-pump the retort, (2) to fill it with nitrogen at pressure, and (3) to allow injection of hydrogen. It was guaranteeing a high level of safety.
The ROOT CAUSE of the explosion was identified in the failure of the operator to effectively evacuate the retort and backfill with nitrogen, combined with a hydrogen purge far short of the specified value.- Root causes
- Date entry in HIAD
- 01/01/2017
Facility
- Application
- Laboratory / R&D
- Sub-application
- particles physics research centre
- Hydrogen supply chain stage
- All components affected
brazing retort, vacum pump
- Location type
- Confined
- Location
- industrial area
- Operational condition
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 2
- Post-event summary
One employee experienced hearing loss in one ear and a shoulder injury from being blown into a cabinet.
A second employee was checked by Medical and authorized to return to work.
Lesson Learnt
- Lesson Learnt
The failure to apply the appropriate procedure suggested the need for either additional administrative controls and/or periodic refresher training.
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Probable IGNITION SOURCE
- Explosion type
References
- Sources categories
- Investigation report
- Reference & weblink
Internal report SAN--SU-SLAC-1996-0005, not available anymore
Also uptaken in US database H2TOOLS
https://h2tools.org/lessons/hydrogen-retort-explosion
(accessed December 2025)