Event
- Event ID
- 401
- Quality
- Description
During a filling at a hydrogen refuelling station, the station was shut down due to a gas detection. The leak was extremely small and difficult to locate but the gas was directed upwards towards the gas sensor which shut down the station. The safety equipment performed well as it should and safely shutdown the station. The tiny leak was located about 8 cm from the end fitting in the middle of the hose.
Discovered during inspection.
- Event Initiating system
- Classification of the physical effects
- Unignited Hydrogen Release
- Nature of the consequences
- leak no ignition
- Macro-region
- Europe
- Country
- Norway
- Date
- Component involved
- dispenser (hose)
- Failure mode
- leak, no ignition
- Initiating cause
- material degradation (generic)
- Root CAUSE analysis
It is suspected that the hose failure was due to an extreme temperature swing. It was the first really cold weather we had experienced being between -15 and -18c. The hose was sent back to the manufacturer for testing and no leak was found which was very interesting. The cause was never officially determined but the problem was resolved.
- Root causes
- Date entry in HIAD
- 01/01/2017
Facility
- Application
- Hydrogen refuelling station
- Sub-application
- Hydrogen dispenser
- Hydrogen supply chain stage
- All components affected
High pressure dispenser hose
- Process temperature range [C]
- ambient temperature (-50°C to +50°C)
- Location type
- Unknown
- Location
- unknown
- Operational condition
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Emergency action
All safety equipment operated as designed and shut the system down.
Lesson Learnt
- Lesson Learnt
All safety equipment operated as designed and shut the system down. In fact, if it were not for the hydrogen released, this could be classified as near-miss. Hoses are consumable parts; they damage quickly because they experience frequent pressure cycles characterised by very high pressures differences and temperature gradients. Moreover, they are also subjected to external mechanical stress such as bending and twisting during the filling.
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Release temperature [°C]
- 25
- Probable IGNITION SOURCE
References
- Sources categories
- Investigation report
- Reference & weblink
Source lost