Event
- Event ID
- 390
- Quality
- Description
While a H2 sample was being prepared for an analysis, one of two cryogenic sample bottle disks ruptured and the gas ignited.
- Event Initiating system
- Classification of the physical effects
- Hydrogen Release and Ignition
- Nature of the consequences
- Macro-region
- North America
- Country
- United States
- Date
- -
- Component involved
- PRD (burst disc)
- Failure mode
- premature activation & venting
- Initiating cause
- unknown
- Root CAUSE analysis
A material deficiency in that the disk was extensively corroded and failed under work working gas pressure. Contributing causes were inadequate quality control which failed to detect the corroded disk, and a test set-up which aimed the disk end of the bottle toward technicians.
- Root causes
- Date entry in HIAD
- 01/11/2025
Facility
- Application
- Laboratory / R&D
- Sub-application
- Aerospace
- Hydrogen supply chain stage
- All components affected
LH2 cryogenic bottles
- Process temperature range [C]
- cryogenic temperature (below -50°C)
- Location type
- Unknown
- Location
- unknown
- Operational condition
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Probable IGNITION SOURCE
- Explosion type
References
- Sources categories
- ORDIN
- Reference & weblink
Mishap no 49 in
P. L. Ordin, Review of hydrogen accidents and incidents in NASA operations, 1974, NASA TM X-71565
https://ntrs.nasa.gov/citations/19740020344Hankinson and Lowesmith, Qualitative Risk Assessment of Hydrogen Liquefaction, Storage and Transportation, FCH JU project IDEALHY, Deliverable 3.10 (2013)
confidential