Skip to main content
Clean Hydrogen Partnership

Detonation of hydrogen in vent stack

Event

Event ID
369
Quality
Description

During the pump operation of a liquid hydrogen tanker, the vent valve was opened rapidly and the hydrogen detonated above the vent stack. The rapid valve opening was aimed at initiating a good pumping in the LH2 pump-vaporizer system. The vent valve was then closed, but the stack continued to flow hydrogen, which burned. The tanker pressure was 16 psig (ca. 1.1 bar).

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
North America
Country
United States
Date
-
Component involved
valve (vent)
Failure mode
leak & ignition
Initiating cause
wrong operation
Root CAUSE analysis

Apparently, the hydrogen release was intentional, but the ignition occurred due to the rapid opening of the vent valve. Following the detonation, the fire continued because the flap valve on the vent did not make a tight seal. The Teflon gasket was found scorched. According to the report, the vent stack was not purged allowing for a H2- air mixture in the stack. It is unclear if purging was foreseen by the procedure.

Root causes
Date entry in HIAD
16/11/2024

Facility

Application
Hydrogen transport and distribution
Sub-application
LH2 tanker
Hydrogen supply chain stage
All components affected

vent valve, stack

Process temperature range [C]
cryogenic temperature (below -50°C)
Process pressure range [MPa]
low to medium pressure (below 2 MPa)
Location type
Open
Location
industrial area
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE
Explosion type

References

Sources categories
ORDIN
Reference & weblink

Mishap no 17 in
P. L. Ordin, Review of hydrogen accidents and incidents in NASA operations, 1974, NASA TM X-71565
https://ntrs.nasa.gov/citations/19740020344