Explosion of a model "hot air" balloon.

Event

Event ID
309
Quality
Description

The balloon had a 3.5m external diameter envelope made of anti-tear fabric (same techniques used in full sized balloons of the same company). The inner balloon was a meteorological balloon made of latex.

When starting filling the inner balloon with hydrogen to a target relative pressure of 0.03 barg, a a small rupture of the skin of the latex balloon developed. The leak was noticed and the filling process was stopped. However, by this time some hydrogen had become trapped between the inner latex balloon and the outer fabric envelope. THis hysrogen found an ignition source and exploded.

According to the HSE report, a static discharge provded the energy required to ignite the flammable hydrogen-air mixture. This static electricity could cumulate because the balloon was brought down to the ground and onto a plastic sheet put there to protect the balloon.

The metal cage attached to the underside of the balloon had an earth line, but this had not made contact with the plastic sheet and would not have prevented such an incident.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
United Kingdom
Date
Component involved
balloon
Failure mode
leak & ignition
Initiating cause
unknown
Root CAUSE analysis

INITIATING cause was the leaking of hydrogen from a tearing of the inner balloon shell and its ignition due to static electricity. A reason for the tearing was not provided.

ROOT CAUSE was an inadequate risk assessment, with shortcomings in the design of the exploded ballon, which could allow confined a build-up of leaking hydrogen and in the filling procedures, which were lacking a correct leak-check before filling with hydrogen.

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Other
Sub-application
Weather balloons
Hydrogen supply chain stage
All components affected

balloon

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
ambient pressure (around 0.1 MPa)
Location type
Unknown
Location
unknown
Operational condition
Pre-event occurrences

The event occurred when filling the balloon with hydrogen.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
1
Post-event summary

The cost of damage to property is unknown, but is can be asumedtha tthe full balloon was damaged beyond repair.

Emergency action

Th onsite fire brigade was alerted

Lesson Learnt

Lesson Learnt

A risk assessment had been performed, considered " suitable and sufficient ". It was clearly not considering various aspects the brought to the explosion of the balloon during filling.
One point was probably an underestimation of the hydrogen flow which can quickly be generated through a crack or fissure. The second point was related to the fact that the escaping hydrogen was remaining confined in the space between the internal and external ballon envelopes.
A third point was the relatively low ignition energy of hydrogen, easily produced by static electricity of plastic friction.

Corrective Measures

The filling procedures were modified.
(1) The filling will be only done in a well-ventilated area,
(2) Cotton material will be used on the ground rather than the plastic sheet.
(3) The latex balloon will be thoroughly checked before use for any tear or splits in the latex.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Release pressure [MPa]
0.1
Probable IGNITION SOURCE
Explosion type

References

Sources categories
HSE
Reference & weblink

Event description provided by HSE, original source confidential