Skip to main content
Clean Hydrogen Partnership

Fire at a generator of a power plant

Event

Event ID
280
Quality
Description

Ejection of rotor wedge material lead to vibration induced failure of components, including hydrogen seals. Serious fire resulted from hydrogen leakage, which subsequently lead to an oil fire. Ignition from metal to metal contact between fractured components.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
United Kingdom
Date
Component involved
H2 coolant system (rotating seal)
Failure mode
leak & ignition
Initiating cause
conventional component failure (turbine-generator)
Root causes
Unknown
Date entry in HIAD
28/02/2009

Facility

Application
Power plant
Sub-application
unspecified power plant
Hydrogen supply chain stage
All components affected

turbine, generator, cooling system

Process temperature range [C]
Above ambient temperature (50°C to 100°C)
Location type
Unknown
Location
unknown
Operational condition

Emergency & Consequences

Number of fatalities
0
Number of injured persons
2

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE

References

Sources categories
HSE
Reference & weblink

Event description provided by HSE, original source confidential