Explosion in an ammonia plant

Event

Event ID
211
Quality
Description

The event took place in the on one out of the seven reactors for ammonia synthesis.
The day of the accident, preparation works for the decennial pneumatic test (previous pneumatic test was carried out in 1978) were started on that unit. The reactor was put out of service and a slow pressurisation with process gases (hydrogen and nitrogen) was carried out at ambient temperature. It was necessary to carry out many pneumatic cycles of pressurisation and depressurisation because of leaks from some flanges.
After any cycle, the bolts of the flanges were tightened and a purging with nitrogen at 8 bar was carried out.

Eventually, a slow pressurisation with process gases was in progress at ambient temperature when the explosion occurred, 20 minutes after the start, at an internal pressure of 250 bar.

The explosion caused one fatality and one injury, destroyed the upper part of the column; metallic parts of the reactor were thrown in a radius of many metres around it. It also caused the complete destruction of the building where the reactor was located.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
Italy
Date
Component involved
reactor / oven / furnace / test chamber
Failure mode
internal explosion
Initiating cause
unknown
Root CAUSE analysis

The original investigation report is not available. According to the eMARS report (see reference), some experts suggested the possibility that accident occurred due to an internal explosion (deflagration) in the reactor.
The ROOT CAUSE could be tentatively attributed to an inadequate testing procedure (too long period between testing, use of flammable gas for testing, failure to correctly identify hazards and mitigate risks)

Root causes
Date entry in HIAD
01/01/2021

Facility

Application
Chemical industry
Sub-application
Ammonia production
Hydrogen supply chain stage
All components affected

Ammonia synthesis reactor

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Semiconfined
Location
industrial area
Operational condition
Pre-event occurrences

The steel reactor had been manufactured in 1929 and since then It had been regularly tested.

Description of the facility/unit/process/substances

DESCRIPTION OF THE REACTOR
It had a volumetric capacity of 8,000 litres, was 7.7 metres high and had a diameter of 850 mm, with a design pressure of 300 bar.

Emergency & Consequences

Number of fatalities
1
Number of injured persons
3
Currency
Euro
Property loss (onsite)
10.000.000
Post-event summary

The material damages were estimated at approximately 20000 millions of lire (approximately 10 million of euros).
eMARS reports 1 fatality and 3 injuries, ARIA 1 resp. 1, Rigas&Amyotte reports 2 resp. 3, and 15,000 evacuated persons.

Emergency action

After the accident, on-site arrived the local fire brigade and the police. The ammonia production was interrupted. The ammonia production was interrupted and the whole factory was stopped by the authorities to establish the causes of the explosion.
On June 14 the production in the other plants not involved in the explosion started again.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2,
N2
Release temperature [°C]
25
Probable IGNITION SOURCE
Explosion type

References

Sources categories
eMARS
Reference & weblink

Event description in the European database eMARS
https://emars.jrc.ec.europa.eu/en/emars/accident/view/d2b442eb-a58a-f25…
(accessed September 2020)

La Stampa printed edition of 11 June 1988
http://www.archiviolastampa.it/
(accessed Jan 2018)

Event no. 49 of the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/49/
(accessed November 2025)