Release during CGH2 transfer

Event

Event ID
210
Quality
Description

A CGH2 tube trailer was parked at the delivery site and was transferring gaseous hydrogen to a stationary storage system. The transfer hose failed releasing hydrogen, which ignited. The resulting fire melted the valves and rupture discs on all tubes. The emergency action plan was initiated, an immediate evacuation of the area was executed and local fire department notified. The fire was extinguished and evacuation over after several hours.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
North America
Country
United States
Date
Component involved
hose (trailer)
Failure mode
rupture & ignition
Initiating cause
material degradation (generic)
Root CAUSE analysis

The INITIATING CAUSE was the rupture of the flexible hose.

The fire escalated from the hose to the trailer tubes. Their pressure relief system (burst disk) activated as expected in these cases, avoiding further escalation due to over-pressurisation of the tubes. However, the damage of additional valves on the trailer suggests a ROOT CAUSE in a shortcoming of a safety design of the transfer process, which did not consider this possibility and failed to guarantee fire protection to critical components.

Root causes
Date entry in HIAD
24/10/2024

Facility

Application
Hydrogen transport and distribution
Sub-application
CGH2 tube trailer
Hydrogen supply chain stage
All components affected

flexible hose, valves, TPRD, tubes.

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Open
Location
highway or similar
Operational condition
Description of the facility/unit/process/substances

The only data known on the trailer is that it consisted of 34 tubes. Using similar cases as a proxy, tubes nominal pressure was very probably 180 bar, and trailer nominal transport capacity was approximately 250 - 300 kg of hydrogen. If the incident occurred at the start of the transfer, the whole content was lost, vented through the burst disk and the vent stack.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
US$
Property loss (onsite)
70.259
Emergency action

The emergency action plan was initiated, an immediate evacuation of the area was executed and local fire department notified. The fire was extinguished and evacuation over after several hours.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Probable IGNITION SOURCE

References

Sources categories
PHMSA
Reference & weblink

Incident I-1989110463 of the US Pipeline and Hazardous Materials Safety Administration PHMSA:
https://portal.phmsa.dot.gov/analytics/saw.dll?Portalpages&PortalPath=%…
(accessed September 2024)