Skip to main content
Clean Hydrogen Partnership

Explosion in an ammonia plant

Event

Event ID
194
Quality
Description

A release of a mixture of hydrogen, nitrogen and ammonia ignited and exploded in the ammonia synthesis unit. The release was due to a cracked pipe near a flange located at the top of the gas-gas heat exchanger.
The leak immediately ignited, resulting in a powerful explosion followed by a fire, brought under control in less than a hour.
The gas mix consisted in 69% of hydrogen, 23% of nitrogen and 8% of ammonia.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Component involved
pipe (generic)
Failure mode
rupture & ignition
Initiating cause
unknown
Root CAUSE analysis

The INITIATING CAUSE was the release of process gas due to a crack on a pipe connected to a heat exchanger.

The ROOT CAUSE is unknown.

Root causes
Unknown
Date entry in HIAD
01/01/2021

Facility

Application
Chemical industry
Sub-application
Fertilisers production
Hydrogen supply chain stage
All components affected

flange, pipe, heat exxhanger

Process temperature range [C]
High temperature (100°C to 500°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Open
Location
populated area
Operational condition
UNKNOWN
Description of the facility/unit/process/substances

From the provided data: 30C, 300 bar and %vol., a total mass of 130 kg can be calculated, out of wich 14 kg of H2

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Currency
Euros
Property loss (onsite)
1.300.000
Post-event summary

The material damage was assessed between the 3 and the 8 millions of French Francs.
The plant was stopped for 5 weeks.

Emergency action

The operator shut down the compressors and the circulation pumps, and alerted the fire brigade of a neighbouring company. Internal firefighters and external emergency services extinguished the fire within 45 minutes by injecting pressurised nitrogen. After which they focussed on the insulations, which was till burning.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2 69%
N2 23%
NH3 8%
Released amount (kg)
14
Release pressure [MPa]
30
Probable IGNITION SOURCE
Explosion type

References

Sources categories
ARIA
Reference & weblink

Event no 19080 of the French database ARIA