Skip to main content
Clean Hydrogen Partnership

Explosion

Event

Event ID
192
Quality
Description

An explosion without fire or gas emission occurred in the washer of the catalyst activation unit. The unit was stopped for maintenance : 3 external employees were checking the washer. The explosion occurs just after the opening of the manhole on the washer. The employee looking through the hole at this moment was seriously injured.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Component involved
reactor / oven / furnace / test chamber
Failure mode
internal explosion
Initiating cause
run-away reaction
Root CAUSE analysis

One of the possible cause of the explosion could have been to the presence of hydrogen in the washer. Another cause, considered more probable by the ARIA report (see references) could be a secondary reaction or a reaction activation which was still running in the washer.

Root causes
Date entry in HIAD
01/01/2021

Facility

Application
Chemical industry
Sub-application
Inorganic chemicals products
Hydrogen supply chain stage
All components affected

washer, catalyst activation unit, Production of hexamethylenediamine

Location type
Unknown
Location
industrial area
Operational condition
Description of the facility/unit/process/substances

DESCRIPTION OF THE PROCESS
The catalyst was produced with a mixture of aluminium and nickel which reacts with soda to produce Raney nickel and hydrogen. Hydrogen is evacuated by the ventilation and the Raney nickel is transferred in the washer.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
3
Post-event summary

Prevention plans will be improved. The water seal of the washer is separated from the rest of the unit to avoid hydrogen entry.
Evacuation plan will be improved.

Lesson Learnt

Corrective Measures

(1) To eliminate the risk of the accidental presence of hydrogen coming from other part of the installation, hydraulic safeguard of the washer was isolated from the other units;
(2) The incident prevention plan of the factory was improved;
(3) The evacuation rules were reviewed and improved.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Probable IGNITION SOURCE
Explosion type

References

Sources categories
ARIA
Reference & weblink

Event description no 20274 in the French database ARIA.