Explosion at a chlorine electrolyser

Event

Event ID
177
Quality
Description

In a chlorine electrolysis facility, a mixture of oxygen and hydrogen in one of the electrolyser cells a short-circuit ignited causing a deflagration. The cover of the cell was a thin plastic film which broke as planned. The production was stopped.

According to the investigation, the inlet line of the electrolyte in the cell was blocked, which lead to an increase of the temperature in the cell and to the increase of oxygen production. On top of that, the alarm related to temperature control did not function.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Component involved
electrolytic cell
Failure mode
internal explosion
Initiating cause
malfunctioning (electrolyser, cross-over)
Root CAUSE analysis

The INITIATING cause was a malfunction in the cell of a chlorine electrolyser.
Contributing cause was the malfunctioning of the alarm system related to the temperature monitoring of the process.

The root cause was probably an underestimation of this hazard in the safety design of the process. Nevertheless, a correct mitigating measure (weak enclosure to reduce the risk of a e deflagration) operated as designed and limited damage,

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Chemical industry
Sub-application
Chlorine production
Hydrogen supply chain stage
All components affected

electrolyser cells

Process temperature range [C]
Above ambient temperature (50°C to 100°C)
Location type
Confined
Location
industrial area
Operational condition
Pre-event occurrences

A short circuit ignite a mixture of oxygen and hydrogen in an electrolyser cell.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0

Lesson Learnt

Corrective Measures

After the accident, the plant operator put in place a system of monitoring and control of the process performed by on-site teams.
This measure was completed later by the installation of an automatic alarm system. Finally, a study was performed to increase the reliability of the whole monitoring system of the installation.

In-depth data

Release type
gas mixture
Involved substances (% vol)
H2, O2
Release temperature [°C]
25
Probable IGNITION SOURCE
Explosion type
Deflagration

References

Sources categories
ARIA
Reference & weblink

Event description in the French database ARIA
https://www.aria.developpement-durable.gouv.fr/accident/25777/
(access September 2020)