Event

Event ID
167
Quality
Description

Fire on a filter of an autoclave.
The event occurred in a plant for the production of plastics. After catalytic synthesis of amines, the filter of the autoclave was taken out for cleaning. During the removal, the fire started.
The fire was extinguished with water jets and water injection into the reactor vessel. The damages were very limited.

The event was caused by the presence of hydrogen at the top of the reactor, which was also in contact with the filter because the valve aiming at isolation the filter had remained open. The ignition of the hydrogen was probably due to the presence of the catalyst, which is pyrophoric when dry.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
fire
Macro-region
Europe
Country
France
Date
Component involved
valve (shut-off)
Failure mode
fire (generic)
Initiating cause
inadequate or no purge
Root CAUSE analysis

The INITIATING cause was the presence of hydrogen in the filter. The intermediate cause is the failing to close the valve supposed to isolate the filter from the content of the reactor.
A CONTRIBUTING OR ROOT CAUSE reported was related to the procedure in place to prepare the filter for dismantling: it must be cleaned-up under water and then dried under nitrogen, to avoid the too intensive drying of the catalyst which can cause the production of sparks. In that case, the drying by nitrogen purging was longer than foreseen.

Root causes
Date entry in HIAD
28/02/2009

Facility

Application
Chemical industry
Sub-application
Plastics production process
Hydrogen supply chain stage
All components affected

,valve, filter, autoclave for the synthesis of plastic

Location type
Unknown
Location
industrial area
Operational condition
Pre-event occurrences

After catalytic synthesis of an amine, the filter the autoclave was taken out for cleaning.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0
Post-event summary

Only the filter's valve and manometer were damaged.

Emergency action

The fire remained localised on the filter. The operators did not succeed in extinguishing the fire with water jets. The introduction of water directly at the entrance of the filter while closing the exit valve allowed to extinguished the fire.

Lesson Learnt

Corrective Measures

The following actions were taken:
1) reduction of the phase of drying of the catalyst by nitrogen;
2) maintaining the filter continuously under water during the dismantling;
3) emptying all the spaces containing the catalyst;
4) installing a hydraulic safe-guard for the case that the isolation valve does not function;
5) re-training personnel on the procedural instructions.