Event
- Event ID
- 153
- Quality
- Description
While travelling to deliver liquid hydrogen to a customer, a tanker experienced an increase of the internal pressure of the cargo tank. The drivers pulled off the road and at that moment the pressure relief system activated. They operated a diverter valve, transferring the cargo tank to the second redundant pressure relief system. About 150 lbs. (68 kg) of product was lost. The delivery was then continued without further incident.
- Event Initiating system
- Classification of the physical effects
- Unignited Hydrogen Release
- Nature of the consequences
- leak no ignition
- Macro-region
- North America
- Country
- United States
- Date
- Component involved
- PRD (burst disc)
- Failure mode
- correct activation & venting
- Initiating cause
- over-pressurisation (boil-off)
- Root CAUSE analysis
The INITIAL CAUSE was probably due to over-pressurisation of the LH2 tank, which triggered a hydrogen venting.
The PHMSA does no report if the over-pressurisation was due to degradation of the vacuum shell. From the fact that the journey continued without further incidents, it could be concluded that the over-pressurisation had been caused during loading of the tanker, so that the ROOT CAUSE could be failure to execute the procedure properly.- Root causes
- Date entry in HIAD
- 02/02/2025
Facility
- Application
- Hydrogen transport and distribution
- Sub-application
- LH2 tanker
- Hydrogen supply chain stage
- All components affected
PRD
- Process temperature range [C]
- cryogenic temperature (below -50°C)
- Process pressure range [MPa]
- low to medium pressure (below 2 MPa)
- Location type
- Open
- Location
- highway or similar
- Operational condition
- Pre-event occurrences
The PHMSA reports a loss of 150 lbs, i.e. 68 kg. On the contrary, the PHMSA corresponding column report a loss of only 18.8 LGA, i.e. 5 kg. Also the transport capacity is doubtful, 1437.5 LGA, corresponding to only 385 kg, which is ten time less than the usually transported values.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
- Currency
- US$
- Property loss (onsite)
- 135
- Post-event summary
Less than 100 kg of hydrogen was lost.
- Emergency action
The dirvers swithed the tank safety system to the an alternative, redundant one
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Released amount (kg)
- 5
- Probable IGNITION SOURCE
References
- Sources categories
- PHMSA
- Reference & weblink
Incident I-2003071049 of the US Pipeline and Hazardous Materials Safety Administration PHMSA:
https://portal.phmsa.dot.gov/analytics/saw.dll?Portalpages&PortalPath=%…
(accessed September 2024)