Explosion on a test bench for rocket engins

Event

Event ID
138
Quality
Description

An explosion of hydrogen gas occurred on a test bench at a factory manufacturing rocket engins. The effect was perceived several kilometres away.

The explosion was caused by the release of 8 kg of H2 (equivalent to 100 m³ of gas) from a section of gas line a under maintenance. A 6-inch flange had been left open, in addition a remotely-controlled valve was opened accidentally. The explosion was followed by a jet flame fed by additional 16 kg of hydrogen gas (200 m³).

The protrective panels were blown off, and debris was scattered within a 100-meter radius of the bench. No injuries were reported, even among the six employees working within a 10- to 50-meter radius of the explosion.

Event Initiating system
Classification of the physical effects
Hydrogen Release and Ignition
Nature of the consequences
Macro-region
Europe
Country
France
Date
Component involved
valve (generic)
Failure mode
erroneous release & ignition
Initiating cause
wrong operation
Root CAUSE analysis

THE INTIATING CAUSE was an accidental release from a compressed hydrogen supply system under maintenance.
The fact that to achieve this, two independently operated valves were opened, suggests that the ROOT CAUSE was not only due to a human error, but to shortcoming in the operative procedures prescribing what to do before and during maintenance. In fact, the hydrogen supply system affected by the explosion had just been used to a purpose different from its main application. it was probably not in the status expected by the team performing maintenance.

Root causes
Date entry in HIAD
10/01/2026

Facility

Application
Non-road vehicles
Sub-application
Aerospace
Hydrogen supply chain stage
All components affected

valves, test bench

Process temperature range [C]
ambient temperature (-50°C to +50°C)
Process pressure range [MPa]
medium to high pressure (10 to 50 MPa)
Location type
Semiconfined
Location
industrial area
Operational condition
Pre-event occurrences

During the day, the damaged test bench, mainly used for testing turbopumps and generators, had been used for one of its secondary functions: supplying gaseous hydrogen at 200 bar to another test bench. To this purpose, liquid hydrogen was first evaporated and then compressed to 800 bar.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Release temperature [°C]
25
Release pressure [MPa]
20
Probable IGNITION SOURCE
Explosion type

References

Sources categories
ARIA
Reference & weblink

HIAD_138 - event no. 31335 of French ARIA database
https://www.aria.developpement-durable.gouv.fr/accident/31355/
(accessed December 2025)