Hydrogen relase from a metal treatment furnace

Event

Event ID
125
Quality
Description

The event occurred at a pit furnace for metal component treatments. The hydrogen feed system for the furnace developed a leak, located on the hydrogen dryer inside a shack attached to a building.
The leak vented hydrogen at 200 psig (approximately 15 bar) into the shack. The hydrogen low-pressure alarm sounded. No furnace operators were present at the time. An estimated 10,000 standard cubic feet (25 kg) of hydrogen vented.

The hydrogen release was caused by a failure of an elastomeric pressure seal on the body of a particulate filter located in the hydrogen supply circuit of the pit furnace.

A month earlier the same incident happened and was identified as a simple seal failure. However, an independent engineering review after the present incident showed the cause to be system overpressure, caused by the failure of a regulator.

Event Initiating system
Classification of the physical effects
Unignited Hydrogen Release
Nature of the consequences
leak no ignition
Macro-region
North America
Country
United States
Date
Component involved
joint/connection (gasket)
Failure mode
leak, no ignition
Initiating cause
over-pressurisation
Root CAUSE analysis

The INITIATING CAUSE was the damage to a seal, which started leaking. The reason for the damage was the malfunctioning of a pressure regulator, which caused overpressure to the low-pressure part of the hydrogen supply system.

The high-pressure part had been revamped and renovated, but the medium-low pressure part was still consisting in the original setting, including the high-to-low pressure interconnecting component.
Therefore, the ROOT CAUSE could be identified in shortcoming when re-designing the installation.

Root causes
Date entry in HIAD
30/12/2025

Facility

Application
Steel and metals industry
Sub-application
pit furnace treatment
Hydrogen supply chain stage
All components affected

pit furnace, pressure regulator, gasket

Process pressure range [MPa]
low to medium pressure (below 2 MPa)
Location type
Confined
Location
industrial area
Operational condition
UNKNOWN
Pre-event occurrences

Part of the hydrogen supply system had been renewed.

Emergency & Consequences

Number of fatalities
0
Number of injured persons
0

Lesson Learnt

Corrective Measures

The plant manager took the decision to have an independent engineering review after the second incident, as essential step to more long-range corrective actions.

In-depth data

Release type
gas
Involved substances (% vol)
H2 100%
Released amount (kg)
215
Release pressure [MPa]
1.5
Probable IGNITION SOURCE

References

Sources categories
H2TOOLS
Reference & weblink

Events in database H2TOOLS
https://h2tools.org/lessons/hydrogen-furnace-leak
(accessed December 2025)