Event
- Event ID
- 125
- Quality
- Description
The event occurred at a pit furnace for metal component treatments. The hydrogen feed system for the furnace developed a leak, located on the hydrogen dryer inside a shack attached to a building.
The leak vented hydrogen at 200 psig (approximately 15 bar) into the shack. The hydrogen low-pressure alarm sounded. No furnace operators were present at the time. An estimated 10,000 standard cubic feet (25 kg) of hydrogen vented.The hydrogen release was caused by a failure of an elastomeric pressure seal on the body of a particulate filter located in the hydrogen supply circuit of the pit furnace.
A month earlier the same incident happened and was identified as a simple seal failure. However, an independent engineering review after the present incident showed the cause to be system overpressure, caused by the failure of a regulator.
- Event Initiating system
- Classification of the physical effects
- Unignited Hydrogen Release
- Nature of the consequences
- leak no ignition
- Macro-region
- North America
- Country
- United States
- Date
- Component involved
- joint/connection (gasket)
- Failure mode
- leak, no ignition
- Initiating cause
- over-pressurisation
- Root CAUSE analysis
The INITIATING CAUSE was the damage to a seal, which started leaking. The reason for the damage was the malfunctioning of a pressure regulator, which caused overpressure to the low-pressure part of the hydrogen supply system.
The high-pressure part had been revamped and renovated, but the medium-low pressure part was still consisting in the original setting, including the high-to-low pressure interconnecting component.
Therefore, the ROOT CAUSE could be identified in shortcoming when re-designing the installation.- Root causes
- Date entry in HIAD
- 30/12/2025
Facility
- Application
- Steel and metals industry
- Sub-application
- pit furnace treatment
- Hydrogen supply chain stage
- All components affected
pit furnace, pressure regulator, gasket
- Process pressure range [MPa]
- low to medium pressure (below 2 MPa)
- Location type
- Confined
- Location
- industrial area
- Operational condition
- UNKNOWN
- Pre-event occurrences
Part of the hydrogen supply system had been renewed.
Emergency & Consequences
- Number of fatalities
- 0
- Number of injured persons
- 0
Lesson Learnt
- Corrective Measures
The plant manager took the decision to have an independent engineering review after the second incident, as essential step to more long-range corrective actions.
In-depth data
- Release type
- gas
- Involved substances (% vol)
- H2 100%
- Released amount (kg)
- 215
- Release pressure [MPa]
- 1.5
- Probable IGNITION SOURCE
References
- Sources categories
- H2TOOLS
- Reference & weblink
Events in database H2TOOLS
https://h2tools.org/lessons/hydrogen-furnace-leak
(accessed December 2025)